Ari Capacities - Payne PH1S Manual

Split system heat pump with air handling unit
Table of Contents

Advertisement

OUTDOOR
UNIT
PH1S
090
Bels — Sound Level (1 bel = 10 decibels)
Cap. — Total Net Capacity (1000 Btuh)
COP — Coefficient of performance =
Unit Power Input × 3.413
EER — Energy Efficiency Ratio =
*Air Conditioning & Refrigeration Institute.
NOTES:
1. Standard ratings are net values, reflecting the effects of circulating fan heat.
Supplementary electric heat is not included. Ratings are based on:
Cooling Standard: 80 F db (dry bulb), 67 F wb (wet bulb) indoor entering-air
temperature and 95 F db entering-air outdoor unit.
Hi-Temp Heating Standard: 70 F db indoor entering-air temperature and
47 F db/43 F wb entering-air outdoor unit.
Lo-Temp Heating Standard: 70 F db indoor entering-air temperature and
17 F wb/15 F db entering-air outdoor unit.
Rated in accordance with ARI Standard 210/240-89.
2. Sound ratings are in accordance with ARI Standard 270-84.
ARI* CAPACITIES
COOLING
INDOOR
AIRFLOW
UNIT
(Cfm)
Net Cap.
PF1B
(Btuh)
090
3000
86,000
LEGEND
Btuh Output
Btuh input
Btuh output
(Based on ARI conditions)
Btuh
Unit Power Input
UNIT
OPERATING
PH1S
WEIGHT (Total)
090
540
Weight Distribution
HEATING
Hi-Temp
Low-Temp
Net Cap.
Net Cap
EER
COP
(Btuh)
(Btuh)
9.8
83,000
3.0
46,000
or
(Based on ARI conditions)
WEIGHT (lbs)
Leg Location
1
2
3
4
175
133
132
100
5
SOUND
RATING
(Bels)
COP
2.0
9.2