Electrical Data - Payne PH1S Manual

Split system heat pump with air handling unit
Table of Contents

Advertisement

UNIT
V-PH-HZ
208/230-3-60
PH1S090
460-3-60
LEGEND
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (Fuse Only)
RLA
— Rated Load Amps
UNIT
V*-PH-HZ
PF1B
208/230-1-60
090
208/230-3-60
460-3-60
LEGEND
FLA
— Full Load Amps
Hp
— Horsepower
MOCP — Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.

ELECTRICAL DATA

OUTDOOR UNIT
VOLTAGE RANGE
Min
Max
LRA
187
254
160
414
508
INDOOR UNIT
VOLTAGE
LIMITS
187-253
187-253
414-528
15
COMPR
FAN MOTORS
No. of
RLA
Fans
31.5
1
80
15.7
1
FAN MOTOR
Hp
FLA
2.4
11.0
2.4
5.8
2.4
2.6
POWER SUPPLY
Min Ckt
MOCP
FLA
Amps
(Amps)
3.1
42.5
50
1.4
21.0
25
POWER SUPPLY
Minimum
MOCP
Circuit
(Amps)
Amps
13.8
20
7.3
15
3.3
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pf1b

Table of Contents