DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS (continued)
Follow correct option according to venting method.
Connecting Directly to Fireplace
If the air inlet and flue outlet tubes are to be connected directly to
the unit (no rigid venting system is being used), then the gasket
provided must be used to seal the 4" (102mm) flue outlet tube.
Peel the paper off the self-adhesive gasket and then wrap it around
the end of the tube (if tube was cut, it is recommended to use cut
end) as shown in Figure 62. Pull the gasket tight at all times while
wrapping it around tube. The gasket ends should align, to form a
complete seal. The overlapped section should NOT come in con-
tact with the seam in the tube. Apply high temperature sealant to
the opposite end of the tube (on the inside of the tube). The end
with the gasket will attach to the back of the unit.
PARTS LIST
INDEX
PART
NUMBER
NUMBER
1
DV769
2
19193
3
19194
4
DV524
5
19196
6
20527
31447-5-0214
DESCRIPTION
Vent Cap Assembly
Outside Mounting Plate
Air Inlet Tube
Flue Outlet Tube
Firestop/Thimble Assembly
Gasket
Connecting to Rigid Vent System
If the air inlet and flue outlet tubes are to be connected to a rigid
venting system (and not directly to the back of the unit), then do
not use the gasket provided. High temperature sealant should be
applied to the outside of the 4" diameter (102mm) flue outlet tube
(if tube was cut, it is recommended to use cut end) and to the in-
side of the tube on the end that connects to the vent cap.
Page 41