Empire Comfort Systems DVP36FP3 Installation Instructions And Owner's Manual page 19

Direct vent zero clearance gas fireplace heater
Hide thumbs Also See for DVP36FP3:
Table of Contents

Advertisement

MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW OFF TOP OF FIREPLACE
FIREPLACE
HARD ELBOW DIMENSIONS
SERIES
"A"
DVP36FP
43-1/2"
(1105mm)
FIREPLACE
FLEX PIPE 90 DEGREE BEND
SERIES
"A"
DVP36FP
45"
(1143mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 11" (280mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. See Figure 26. When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination. See Figure 27.
31447-5-0214
Figure 26
"B"
"C"
4-1/2"
6-1/2"
(114mm)
(165mm)
"B"
"C"
4-1/2"
6-1/2"
(114mm)
(165mm)
Figure 27
Figure 28
Page 19