Masonry Installations - Rinnai Neo RIB2310N Installation Manual

Hide thumbs Also See for Neo RIB2310N:
Table of Contents

Advertisement

Masonry installations

1. Check dimensions of the opening
Refer 'Enclosure dimensions' and if necessary bring them to the required dimensions.
Check the chimney height as inadequate height can effect product performance. Some
installations may require the chimney height to be extended to reduce down drafts.
2. Check flueway
• Ensure there are no obstructions
• Provide a firm, flat and sealed base (sealed means no holes or openings in the fireplace)
• Ensure adequate support of the appliance (if not properly supported noise and vibration
may result)
3. Install flexiliner flue system
To ensure adequate draw for maximum performance of the appliance, Rinnai strongly
recommends the use of a Rinnai flexiliner flue system for masonry installations. Failure to meet
this installation criteria may result in an unsafe situation. Performance issues resulting from
inadequate flueing is not covered by the warranty.
Installation without a flexiliner is permissible in masonry installations as long as the chimney
has been checked for soundness and ability to achieve a good draw.
Masonry installation without a flexiliner flue
Inbuilt masonry without a flexiliner flue
Chimney plate
Mortar
Rinnai New Zealand Limited
Masonry installation with a flexiliner flue
Inbuilt masonry with a flexiliner flue
Approved chimney
cowl
Minimum
200 mm
Minimum
3.6 m
Flexible chimney
liner
Appliance
adaptor
Approved chimney
cowl
Chimney plate
Mortar
Adaptor
14
Minimum
200 mm
Minimum
3.6 m
Neo Installation Manual: 11906-B
02-11