Program example for resetting the inverter at inverter error

The following is a program example for resetting station 1 inverter.
X0
X0F
X1
0
M0 X101A X20
7
Error status flag
11
NOTE
• The above inverter reset using RY1A may be made only when an inverter error occurs. When Pr.349
Communication reset selection = "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RYF) with the instruction code (HFD) and data (H9696) to reset
the inverter, set a value other than "0" in Pr.340 Communication startup mode selection (refer to
change the operation mode to the network operation mode. (For the program example, refer to
• Refer to
page 35
86
PROGRAMMING EXAMPLES
SW80.0
for operation conditions of inverter reset.
M0
Check the data link status of the station 1
Turn on the error reset request flag (RY1A)
Y101A
Turn off the error reset request flag (RY1A)
when the error status flag (RX1A) is off.
END
page
27) or
page
78)