8.1
Program example for reading the inverter status
The following program turns on Y00 of the output unit when station 1 inverter is running
X0
X0F
X1
0
M0
X1002
7
Inverter running (RX02)
10
Remote input
RXF
to
One
station
RX1F
to
These signals are initial values. You can change output signals using Pr.190 to Pr.196, Pr.313 to Pr.315 (output terminal function
selection.)
SW80.0
X100F
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
RX0
0
0
0
RX10
Inverter status
b0: During forward rotation
b1: Reverse running
b2: Running (RUN)∗1
b3: Up to frequency (SU)∗1
b4: Overload alarm (OL)∗1
b5: Instantaneous power failure (IPF)∗1
b6: Frequency detection (FU)∗1
b7: Fault (ABC1)∗1
b8: ─ (ABC2)∗1
b9: ─ (DO0)∗1
b10: ─ (DO1)∗1
b11: ─ (DO2)∗1
M0
Check the data link status of the station 1
Turn on the output unit (Y00)
Y30
END
0
0
0
0
0
0
0
0
[Inverter status]
PROGRAMMING EXAMPLES
X1000
0
0
0
0
0
8
77