7.3
Torque command by CC-Link communication
Digital torque command can be given during torque control under Real sensorless vector control and vector control using the
FR-A8NC. The torque command setting method can be selected using Pr.804 Torque command source selection.
Pr.
Name
Torque command
804
source selection
Can also be set from operation panel or parameter unit.
Initial
Setting
value
range
0
Torque command by terminal1 analog input
Torque command by CC-Link communication (FR-A8NC)
1
• Torque command by parameter setting
Setting value of Pr.805 or Pr.806 (-400% to 400%)
Torque command by CC-Link communication (FR-A8NC)
• Torque command by parameter setting
3
Setting value of Pr.805 or Pr.806 (-400% to 400%)
• Setting is available using the remote register RWw1 or RWwC.
(-400% to 400%)
0
4
16 bit digital input (FR-A8AX)
Torque command by CC-Link communication (FR-A8NC)
• Torque command by parameter setting
5
Setting value of Pr.805 or Pr.806 (-327.68% to 327.67%)
• Setting is available using the remote register RWw1 or RWwC.
(-327.68% to 327.67%)
Torque command by CC-Link communication (FR-A8NC)
6
• Torque command by parameter setting
Setting value of Pr.805 or Pr.806 (-327.68% to 327.67%)
Torque command
DETAILS OF INPUT AND OUTPUT SIGNALS
Parameter for
speed limit
Pr.807
Pr.808, Pr.809
Pr.807
Pr.808, Pr.809
Pr.807
71