REASSEMBLING THE THERMOSTAT TO THE INSTALLED BACKPLATE
Before the thermostat is reassembled to the backplate, ensure the following:
* Polarity has been respected for the communication wires.
* All wires for peripheral components (SL-IDS, perimeter heat) are connected.
* Ensure all wires are properly inserted and screwed down in terminal blocks.
* Ensure dipswitches are set appropriately
Reassemble the thermostat as follows:
1. Position the housing assembly inside the access panel.
2. Position the housing and access panel assembly on the hinged tabs located at the top of the
installed backplate.
3. Gently swing the thermostat and access cover downwards and press on the bottom center
edge until it snaps into place.
NOTE: TEMPERATURE ACCURACY
Full temperature accuracy will only be realized after the thermostat has been installed and pow-
ered for at least one (1) hour.
11