THERMOSTAT INSTALLATION: DSL-520P

LOCATION

The most important consideration in installing your DSL-520P Communicating Zone thermo-
stat is where to locate the unit. The location can radically affect the operation of the thermo-
stat. To ensure proper operation, the thermostat should be mounted on an inside wall in a
frequently occupied area of the zone. In addition, its position must be at least 18 inches (46 cm)
from any outside wall, and approximately 5 feet (1.5 m) above the floor in a location with
freely circulating air of an average temperature.
BE SURE TO AVOID THE FOLLOWING LOCATIONS:
* behind doors or in corners where freely circulating air is unavailable
* where direct sunlight or radiant heat from appliances might affect control operation
* on an outside wall
* adjacent to, or in line with, conditioned air discharge grilles, stairwells, or outside doors
* where its operation may be affected by steam or water pipes or warm air stacks in an
adjacent partition space, or by an area not heated or cooled behind the thermostat
* where its operation will be affected by the supply air of an adjacent unit
* near sources of electrical interference such as arcing relay contacts