6-2. Operation Data

<Cooling>
Temperature
condition (°C)
Indoor
Outdoor
27/19
35/–
<Heating>
Temperature
condition (°C)
Indoor
Outdoor
20/–
7/6
Note :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5m
Standard
Model
pressure
name
P (MPa)
10UKV-E
1.1
Standard
Model
pressure
name
P (MPa)
10UKV-E
2.4
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
13.5
49
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
40
0
– 19 –
FILE NO. SVM-02007
Indoor
Outdoor
Compressor
fan
fan
revolution
mode
mode
High
High
Indoor
Outdoor
Compressor
fan
fan
revolution
mode
mode
High
High
(rps)
54
(rps)
70