Mains Electricity Connection

Warning! this appliance must be earthed
We recommend that the appliance is connected by a qualified electrician, who is a member of the N.I.C.E.I.C. and who will comply
with the I.E.E. and local regulations.
This hob is intended to be connected to permanent, fixing wiring and dependent on the power configuration is intended to be
connected to a 13A supply or connected via a 13A plug. The table below shows the recommended size of cable and the fuse that
will be required for each power configuration mode.
Power configuration mode
2.8kW
3.5kW
6.0kW
7.2kW
The following diagram shows the main connection terminal block: (use the diagram from the HCC561 manual)
Terminal connections:
1&2: Live (linked)
4: Neutral
: Earth
2.8kW mode
When the hob is configured in 2.8kW mode it can be connected via a
standard 13A switched fused spur.
3.5kW-7.2kW modes
When configured in any mode other the 2.8kW, the hob should be installed
into a dedicated cooker outlet and protected by the size of fuse shown in the
table above.
This appliance is intended to be connected to fixed wiring by a double pole
switch, having a contact separation of at least 3mm in all poles. The switch
must be positioned no further than 2m from the appliance.
Please note:
The mains cable must only be replaced by a qualified electrician or service engineer and be of a cross sectional area appropriate
for the power configuration mode of the hob, as shown in the table above.
The marking of the current rating of the fuse or circuit breaker protecting this appliance should be marked on the socket outlet.
Assembly and electrical connection should be carried out by specialised personnel.
When installing this product we recommend you seek the help of another individual.
Ensure that the brass links are securely fitted. Failure to do so will prevent the hob from operating correctly.
Any service call arising from incorrect installation may result in a charge.
Mains cable size (CSA, mm2)
1.5
1.5
2.5 - 4.0
2.5 - 4.0
Fuse protection required
13
16
25
32
Fig.6
13