6.2 Normal with first switching on or power failure
In case of fault when the appliance is switched on for the first time or in case of a power failure, one of the two
conditions described below occurs:
1. If the internal temperature is higher or the same as the sensor cut-in temperature (CUT-IN), when the power
is restored, the electronic board activates the compressor and the fan till the set temperature is reached and
after 5 hours the electronic board activates the defrosting procedure (after the compressor cut-out)
2. If the internal temperature is lower than the sensor cut-in temperature (CUT-IN), when the power is restored,
the compressor functions in thermostatic conditions and after 5 hours the electronic board activates the de-
frosting procedure (after the compressor cut-out)
The electronic board activates, in any case, the defrosting procedure 5 hours after the first switching on and
after a power failure.