Function and Control
After energization, the motor of upper and lower swing will enable the air
deflector to be open and then be close completely. And the air outlet is close.
In heating mode, if the swing function is not set, the upper and lower air
deflector will rotate to maximum in clockwise direction. Then it will rotate
to place D. Under other state, the upper and lower air deflector will rotate to
level L. If the swing function is set when starting the unit, the air deflector
will swing between place L and D. there are 7 states for air deflector: in
Place L, Place A, Place B, Place C, Place D, and swing between Place L and
place D, stop in any place between Place L and place D. When the unit is
turned off, the air deflector will stay in place 0. The swing is available only
when the swing function is set and the indoor fan is running.
Note: When place L to B, place A to C, and place B and D is set, the air
deflector will swing between place L to D.
O(0°)
1. It is applicable to cooling mode, dehumidifying mode and heating mode.
2. In cooling mode or dehumidifying mode, 1 hour after the sleep curve is
set, the setting temperature will rise by 1 ¡æ. 2 hours later, the setting
temperature will rise by 2 ¡æ. After that, the setting temperature will not
change any more
set
set
set
1h
3. In heating mode, 1 hour after the sleep curve is set, the setting temperature
will decrease by 1 ¡æ. 2 hours later, the setting temperature will decrease by
2 ¡æ. After that, the setting temperature will not change any more.
1h
set
set
set
The main board has general timer function and clock function. The timer
function can be selected by remote controller with different function
(1) General timer (start and stop time can be set. The accuracy is minute.
E.g.: timer on for 1 hour; timer off for 1.5 hours.)
Timer on: after setting timer on, the unit will run at setting time according to
the original setting mode. The timing interval is 0.5hour, and the setting
range is 0.5~24hours.
L
A
B
C
D
Set temp. T
2h
About 2h
2h
About 2h
Set temp. T
set
Timer off: the timer off function can be set when the unit is on. When the
setting time for timer off is reached, the unit will stop. The timing interval is
0.5hour, and the setting range is 0.5~24hours.
Clock (start and stop time can be set. The accuracy is minute. E.g.: timer
on at 8:00a.m.; timer off at 17:30p.m.)
Timer on: if the timer on function is set when the system is on, the system
will go on running. If the timer on function is set when the system is off, the
system will start running in the previously set mode when the setting time is
reached.
Timer off: if the timer off function is set when the system is off, the system
will keep off even though the setting time is reached. If t he timer off
function is set when the system is on, the system will stop running when the
setting time is reached.
Timer modification: when the system is under timer state, start or stop of the
unit can be set via remote ON/OFF button and the timer can be reset. The
system runs according to the latest setting state.
When both the timer on and timer off are set: the system runs according to
the current setting state. When the setting time is reached, the unit will start
and stop running. In that case, the unit will run according to the previously
setting mode when the setting time for timer on is reached. The unit will stop
running while the setting time for timer off is reached.
If the setting time for timer on and timer off is the same, the unit will stop
running no matter what the current state is.
Memory: mode, up and down swing, light, setting temperature, setting fan
speed, general timer (not clock), Fahrenheit / Celsius. After de-energized,
the unit can run according to the memory if it is energized again. If the timer
function is not set in the last remote control, the system will run according to
the last remote control. If the timer function is set in the last control before it
is de-energized, the system will memorize the last timer setting. The setting
time is recalculated since the energization of the unit. If the timer function is
set in the last control and the setting time is reached before the unit is
de-energized, the unit will run according to the previous running mode after
it is energized again. But the timer function will terminate. The clock will
not be memorized.
(11) Turbo function
In cooling and heating mode (not available in auto, dehumidify, fan mode),
set
press the Turbo button, the fan speed displayed super high speed in the
remote controller and the indoor fan rotates at super high speed.
(12) Health function
When the indoor fan motor is running, the Health function is set by pressing
remote controller (If there is no Health button on the remote controller, the
Health function opening is defaulted).
(13) I Feel function
If the remote controller receives the I Feel order, the controller will work at
the ambient temperature value which is sent by remote controller (Except the
defrosting and anti-cool wind, which still adopts the sampling value of AC
itself ambient temperature sensor), the remote controller will send ambient
temperature value to controller at intervals. If the controller hasn't received
the ambient temperature value from the remote controller for long time, then
it will run accroding to the current ambient temperature of AC. If the
function has not been set, the ambient temperature will adopt the sensor
sampling value of AC itself. If power off happens, this function will not be
memorized.