For detaching the indoor unit from the installation plate pull the
indoor unit toward you while pushing the bottom up at the speci-
fied places.
Push
4)Run the drain hose at a downward sloped angle.
Do not rise the drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
5)Put water in the drain pan and make sure that the water is
being drained outside.
Caution:
Install the drain pipe for proper drainage. Improper drainage can
result in water dripping inside the room.

7.4 INSTALLATION OF OUTDOOR UNIT

* Holes are provided on the base plate of the outdoor unit to
ensure that the defrost water produced during heating opera-
tions is drained off efficiently.
* If a centralized drain is required when installing the unit on a
balcony or wall.
* If the drain port is covered by a mounting base or floor surface,
place additional foot bases of at least 30mm in height under the
outdoor unit's feet.
* In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating
performance.)
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
Remove the Valve cover from the unit by loosening the screw.
Align the center of the pipings and sufficiently tighten the flare
nut by hand.
32
Push
Do not form the drain hose
into the waved shape.
Do not put the drain
hose end in the
drainage ditch.
Drain-water hole
Finally, tighten the flare nut with torque wrench until the wrench
clicks.
Outdoor unit
2.Overlap the connection pipe insulation material and the indoor
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
After the piping has been connected to the indoor unit, perform
the air purge.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor
unit using a vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the vacuum pump manual.
Air purging with vacuum pump
Be sure to use a vacuum pump with counter-flow prevention
function so that oil inside the pump does not flow back into the
air conditioner pipes when the pump stops. (If oil inside the
vacuum pump enters into the air conditioner circuit which uses
R410A, trouble with the refrigeration system may develop.)
1. Connect the charge hose from the manifold valve to the service
port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold
valve.
Installation Manual
Liquid side piping
(Smaller diameter)
Torque wrench
Gas side piping
(Bigger diameter)