Check Code 1C (Miswiring In Indoor/Outdoor Units) - Toshiba RAS-07PKVP-E Service Manual

Split type
Hide thumbs Also See for RAS-07PKVP-E:
Table of Contents

Advertisement

High Wall, Heat Pump Type

10-8.Check Code 1C (Miswiring in Indoor/Outdoor Units)

and 1E
Check procedure
Is connecter of coil connected to inverter?
Is positioning sound of valve (sound hitting to stopper) heard
from valve when the air conditioner starts the operation after turning off power
Are temp. sensors of indoor/outdoor units correctly set to the holder?
NOTE :
The temperature sensors which are used to control pulse motor valve
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.
sensor (TE), outdoor suction temp. sensor (TS) and outdoor sensor (TO).
Gas amount check and valve clogging check
Remove TC sensor connector from the P.C. board in indoor unit.
(Remove connector from the P.C. board.)
Operate the air conditioner in COOL mode by TEMP button
("Beep" sound is heard if keeping pushed for 10 seconds.).
The operation enters temporary operation mode which fixes opening degree of compressor speed.
Check condensation at outlet of PMV, and then check operating pressure from the service port.
Existence of condensation at outlet of P.M.V.
If there is condensation at outlet (1/4 inch=Ø6.35mm valve side),
Check the operating pressure from service port, and add gas if pressure is low.
1C
Gas leakage,
disconnection of TS/TC
sensors (Check code 02, 1C)
Valve drive check
Is coil of the pulse motor valve
(P.M.V.) correctly set?
YES
YES
of the air conditioner once?
YES
YES
the valve is clogged.
1E
Discharge temp. error,
gas leakage
(Check code 03, 1E)
NO
NO
NO
NO
YES
85
Service Manual
Set it correctly.
Set it correctly.
Replace coil valve.
Set it correctly.
Replace valve.
Add gas.