High Wall, Heat Pump Type
• For detaching the indoor unit from the installation
plate pull the indoor unit toward you while pushing
the bottom up at the specified places.
Push
Push
9-3-7. Drainage
1) Run the drain hose at a downward sloped
angle.
NOTE
Hole should be made at a slight downward slant on the
outdoor side.
50 mm or
more
Do not route the
drain hose upwards.
Do not form the drain
hose into a waved shape.
2) Put water in the drain pan and make sure that
the water is being drained outside.
Press (unhook)
Do not put the drain hose
end into water.
Do not put the drain hose
end in a drainage ditch.
3) When connecting extension drain hose,
insulate the connection part of extension drain
hose with shield pipe.
Shield pipe
Inside the room
Drain hose
Install the drain pipe for proper drainage. Improper
drainage can result in water dripping inside the room.
This air conditioner has been designed to drain water
collected from condensation which forms on the back
of the indoor unit, to the drain pan.
Therefore, do not locate the power cord and other parts
at a height above the drain guide.
Space for pipes
64
Service Manual
Extension drain hose