High Wall, Heat Pump Type

8-3-2. In Heating Operation

(This operation controls the fan speed at the indoor unit
side.)
The indoor fan (cross flow fan) is operated by the
phase control induction motor. The fan rotates in 5
stages in MANUAL mode, and in 5 stages in AUTO
mode, respectively.
(Table 1)
HEAT ON
Fan speed setup
AUTO
YES
TC
42°C
(Fig. 4)
NO
* Fan speed =
a : In up operation 1, in down operation 0
(Fig. 5)
Basic fan control
TA - Tsc
b
[°C]
c
–0.5
d
–1.0
e
–1.5
f
–2.0
g
–2.5
–5.0
–5.5
*1: Fan speed = (M+–L+)x1/5+L+
*2: Fan speed = (M+–L+)x2/5+L+
*3: Fan speed = (M+–L+)x3/5+L+
*4: Fan speed = (M+–L+)x4/5+L+
(Calculated with linear approximation from M+ and L+)
*5: Fan speed = (H–M)x1/5+M
*6: Fan speed = (H–M)x2/5+M
*7: Fan speed = (H–M)x3/5+M
*8: Fan speed = (H–M)x4/5+M
(Calculated with linear approximation from H and M)
(Fig. 6)
Cold draft preventive control
TC
46
46
34
45
45
33
33
33
21
32
32
20
*A+4
*A+4
*A+4
*A-4
*A-4
*A-4
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc
24, A is 24, and when Tsc < 24, A is Tsc
Tsc: Set value
MANUAL
(Fig. 3)
Fan speed
Indication
Hi Power
L
W8
W9
L+
(L+M)/2
(L+M)/2
M
WB
WD
M+
(M+H)/2
(M+H)/2
H
WE
WF
Min air flow rate control
Limited to Min WD tap
TC
52
51
*
42
41
No limit
(TC – (40 + a)) / 10 x (WD – W8) + W8
Fan speed
Hi Power
L+ (W9)
M(WB)
*1
*5
*2
*6
*3
*7
*4
*8
M+ (WD)
H (WE)
M+(WD)
Line-approximate
M+ and SUL with Tc.
SUL (W2)
Stop
1) When setting the fan speed to L, L+, M, M+ or
H on the remote controller, the operation is
performed with the constant speed shown in
Fig. 3 and Table 8-3-2.
2) When setting the fan speed to AUTO on the
remote controller, revolution of the fan motor is
controlled to the fan speed level shown in Fig.
5 according to the set temperature and room
temperature.
3) Min. air flow rate is controlled by temperature of
the indoor heat exchanger (TC) as shown in
Fig. 4.
4) Cold draft prevention, the fan speed is
controlled by temperature of the indoor heat
exchanger (TC) as shown in Fig. 6.
In starting and in stability
In starting
• Until 12 minutes
passed after operation
start.
• When 12 to 25 minutes
FAN
passed after operation
AUTO
start and the room
temperature is 3°C or
more lower than the set
temperature.
• Room temperature
FAN
Manual
< Set temperature –4°C
Table 8-3-2 Indoor fan air flow rate (Heating)
RAS-07PKVP-E
RAS-07PKVP-ND
Fan speed
Fan
Air flow
level
speed
(rpm)
(m
WF
1170
WE
UH
1170
WD
H
1070
WC
M+
980
WB
900
WA
M
880
W9
850
W8
L+
750
W7
L
750
W6
L–
650
W5
UL
650
W4
650
W3
SUL
650
W2
560
W1
420
36
Service Manual
In stability
• When 12 to 25 minutes
passed after operation
start and the room
temperature is higher
than the set temperature
–3°C
• When 25 minutes or more
passed after operation
start
• Room temperature
Set temperature –3.5°C
RAS-10PKVP-E
RAS-13PKVP-E
RAS-10PKVP-ND
RAS-13PKVP-ND
Fan
Air flow
Fan
rate
speed
rate
speed
3
3
/h)
(rpm)
(m
/h)
(rpm)
645
1200
665
1240
645
1200
665
1240
575
1100
595
1140
510
1010
530
1050
455
930
475
960
440
880
440
880
420
850
420
850
345
750
345
750
345
750
345
750
275
650
275
650
275
650
275
650
275
650
275
650
275
650
275
650
210
560
210
560
110
420
110
420
Air flow
rate
3
(m
/h)
695
695
625
560
495
440
420
345
345
275
275
275
275
210
110