Vertical; Through The Wall & Vertical - Quadra-Fire CASTILE-MBK-B Owner's Manual Installation And Operation

Quadra-fire castile-b pellet stoves
Hide thumbs Also See for CASTILE-MBK-B:
Table of Contents

Advertisement

Castile-B FS Pellet Stove
C. Vertical
Flashing
Firestop
Ceiling Support
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
Figure 15.1
D. Through The Wall & Vertical
May 12, 2014
Rain Cap
24 in. (610mm) Minimum
6 in. (152mm) Class A
Chimney Connector
Adapter
3 in. (76mm) Min.
6 in. (152mm) Flue
Connector
3 in. to 6 in.
(76-152mm)
Top Vent Kit
Clean-out Cover
2 in. (51mm) minimum
6 in. (152mm)
minimum
Figure 15.2
7021-130F
We recommend a minimum of 60 in.
(1.5m) vertical, however above the eave
is preferred.
Both installations are approved for
mobile home installations. Must use
3 or 4 inch (76 to 102mm) "L" or "PL"
listed pellet venting or listed double
wall pipe and Quadra-Fire Outside Air
Kit in mobile homes. Single wall pipe
is approved for residential installations
only.
Rain Cap
Flashing
24 in. (610mm) minimum
Support Bracket
every 60 in. (1.5m)
Wall Thimble
Tee
Clean-out Cover
Non-combustible Hearth Pad
Page 15