E. Masonry
F. Alternate Masonry
Page 16
Fire Hazard
Inspection of Chimney:
Masonry chimney must be in good condition.
Meets minimum standard of NFPA 211
Factory-built chimney must be minimum 6 in. (152mm)
UL103 HT.
1 in. (25mm) clearance
with firestop
6 in. (152mm)
minimum
Non-combustible Hearth Pad
Figure 16.1
Concrete Cap
1 in. (25mm) clearance
with firestop
6 in. (152mm) minimum
Non-combustible
Hearth Pad
Figure 16.2
WARNING
Concrete Cap
Clean-out cover
7021-130F
Castile-B FS Pellet Stove
Fireclay flue
liner with airspace
Flashing
1 in. (25mm)
clearance
3 in. (76mm)
minimum
Sheathing
Airtight
Clean-out Door
Fireclay Flue Liner
with airspace
Flashing
1 in. (25mm) clearance
2 in. (51mm) minimum
Sheathing
Airtight clean-out door