AIR DUCTS

General Requirements

The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design
Guidelines reference tables available from your local distributor.
The duct system should be sized to handle the required system
design CFM at the design external static pressure. The furnace
airflow rates are provided in Table 7- -Air Delivery- -CFM (With
Filter). When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- - and return- -duct connections to furnace with code
approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
INPUT
RETURN-AIR
SPEED
BTUH
SUPPLY
5(Gry)
4(Yel)
40000
SIDE/BOTTOM
3(Blu)
2(Org)
1(Red)
5(Gry)
4(Yel)
3(Blu)
60000
SIDE/BOTTOM
2(Org)
1(Red)
5(Gry)
4(Yel)
3(Blu)
80000
SIDE/BOTTOM
2(Org)
1(Red)
5(Gry)
4(Yel)
3(Blu)
100000
SIDE/BOTTOM
2(Org)
1(Red)
5(Gry)
4(Yel)
BOTTOM
OR
3(Blu)
120000
TWO SIDES
2(Org)
1(Red)
*A filter is required for each return ---air inlet. Airflow performance included 3/4 ---in. (19 mm) washable filter media such as contained in factory ---authorized
accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. W.C. available external static pressure.
--- Indicates unstable operating conditions.
Table 7 – Air Delivery - - CFM (With Filter)
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1
0.2
0.3
1120
1080
1030
880
845
810
695
665
620
640
595
540
570
525
475
1720
1670
1620
1565
1325
1285
1255
1220
1010
970
925
1160
1115
1080
1045
785
715
655
1810
1770
1720
1665
1535
1500
1475
1435
1380
1340
1305
1270
1180
1130
1095
1060
1100
1045
1010
2040
1970
1885
1795
1550
1505
1460
1415
1780
1730
1690
1645
1345
1295
1250
1195
1390
1350
1295
1260
2275
2230
2185
2130
1875
1820
1770
1720
2170
2125
2075
2025
1475
1420
1350
1280
1625
1565
1505
1445
Ductwork passing through unconditioned space should be
insulated to enhance system performance. When air conditioning is
used, a vapor barrier is recommended.
Maintain a 1- -in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36- -in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further
requirements.

Ductwork Acoustical Treatment

NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take- -off may
require internal acoustical lining. As an alternative, fibrous
ductwork may be used if constructed and installed in accordance
with the latest edition of SMACNA construction standard on
fibrous glass ducts. Both acoustical lining and fibrous ductwork
shall comply with NFPA 90B as tested by UL Standard 181 for
Class 1 Rigid air ducts.
NOTE: For horizontal applications, the top most flange may be
bent past 90_ to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the coil
are performed.
0.4
0.5
0.6
980
925
875
820
780
740
710
680
575
535
495
455
495
460
420
370
425
385
330
255
1505
1440
1375
1185
1145
1115
875
835
785
745
1000
960
920
595
530
490
435
1610
1540
1475
1405
1370
1340
1240
1200
1165
1015
975
935
970
920
885
845
1720
1635
1540
1365
1325
1280
1610
1555
1481
1155
1105
1055
1200
1160
1105
2055
1950
1825
1660
1600
1550
1975
1900
1790
1215
1165
1105
1385
1325
1275
27
0.7
0.8
0.9
760
690
630
640
615
570
420
370
280
310
260
230
220
-
1295
1220
1135
1075
1040
1000
690
660
620
875
840
785
385
340
285
1400
1315
1235
1310
1245
1160
1130
1090
1050
895
850
800
790
745
690
1450
1360
1230
1230
1180
1135
1400
1310
1210
1000
955
915
1050
1010
965
1710
1610
1500
1505
1450
1390
1695
1590
1470
1050
995
930
1225
1170
1130