Horizontal - Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions

Series 100 single stage 4-way multipoise gas furnace
Table of Contents

Advertisement

NOTE: The condensate trap extends below the side of the casing
in the horizontal position. A minimum of 2 in. (51 mm) of
clearance is required between the casing side and the furnace
platform for the trap to extend out of the casing in the horizontal
position.
To Relocate the Condensate Trap:
S Remove the knockout in the casing for the Casing Grommet.
S Install the grommet in the casing.
S Orient the furnace in the desired position.
S Allow for 2 in. (51 mm) of clearance underneath the furnace for
the condensate trap and drain line.
S Fig. 10 shows the condensate trap and tubing before and after
relocation in the horizontal right position.
S Fig. 11 shows the condensate trap and tubing before and after
relocation in the horizontal left position.
S Refer to the appropriate figure to begin the trap conversion.
S Remove the relief tube from the condensate trap.
S Remove the screw that secures the condensate trap to the
collector box.
S Remove the trap.
S Remove the relief tube from the port on the collector box. It is
not necessary to remove the tube from the inducer assembly.
For Horizontal Left only:
S Remove the pressure switch tube from the front pressure switch
and discard the tube. A new pressure switch tube is shipped in
the loose parts bag.
Collector Box
Plugs
Condensate Trap
Relief Port
UPFLOW TRAP CONFIGURATION
1 & 2 Stage Units
Fig. 8 - - Upflow Trap Configuration
For Horizontal Right only:
S The pressure switch tube location is not modified.
S Loosen the clamp around the inlet of the vent elbow on the
inducer.
S Remove the plugs from the collector box and set aside. Do Not
Discard Plugs.
For Horizontal Left only:
S Remove the middle and right plug from the ports at the bottom
of the collector box.
For Horizontal Right only:
S Remove the plug to the right of the condensate trap.
S Refer to the appropriate figure to begin the trap conversion.
S Install the plugs previously removed from the collector box in
the ports where the condensate trap was removed.
S Install the trap over the ports on the lower side of the collector
box.
S Secure the trap to the collector box with the screw.
S Connect the relief tube to the condensate trap to the relief port of
the condensate trap.
S If necessary, slide the relief tube in the inducer stand-offs to
adjust the position of the tube.
S Connect the relief tube to the relief port of the condensate trap.
For Horizontal Left only:
S Connect the new pressure switch tube to the port on the front
pressure switch. Route the tube through the stand-offs on the
inducer assembly and connect to the port on the collector box.
Trim off any excess tube to avoid sags or kinks in the tube.
S Rotate the vent elbow to the desired position and tighten the
clamp 15 in.-lbs.
S Refer to Condensate Drain section for information how to install
the condensate drain.
Vent Pipe Clamp
Pressure Switch
Port
13
Vent Elbow Clamp
Vent Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Condensate Trap
Outlet
A11307