Electrical Data - Carrier 50HS Product Data

Single-package heat pumps 1/2 to 5 nominal tons
Hide thumbs Also See for 50HS:
Table of Contents

Advertisement

Electrical data

UNIT
V-PH-Hz
50HS
018
208/230-1-60
024
208/230-1-60
208/230-1-60
030
208/230-3-60
208/230-1-60
036
208/230-3-60
460-3-60
208/230-1-60
042
208/230-3-60
460-3-60
208/230-1-60
048
208/230-3-60
460-3-60
208/230-1-60
060
208/230-3-60
460-3-60
LEGEND
AWG
— American Wire Gage
CSA
— Canadian Standards Association
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor-Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
RLA
— Rated Load Amps
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker. The
CSA units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
22
COMPRESSOR
OFM
RLA
LRA
FLA
10.4
49.0
0.7
11.2
61.0
1.4
14.4
82.0
1.4
10.4
65.5
1.4
18.0
96.0
1.4
11.4
75.0
1.4
5.4
40.0
0.8
20.4
102.0
1.4
14.0
91.0
1.4
6.4
42.0
0.8
26.4
129.0
2.1
15.0
99.0
2.1
8.2
49.5
1.1
32.1
169.0
2.1
19.3
123.0
2.1
10.0
62.0
1.1
average voltage
452 + 464 + 455
3
1371
=
3
= 457
POWER SUPPLY
IFM
FUSE OR HACR BRK
FLA
MCA
Max
1.8
15.5
25
2.0
17.4
25
2.6
22.0
30
2.6
17.0
25
2.8
26.7
40
2.8
18.5
25
1.4
9.0
10
4.0
30.9
50
4.0
22.9
30
2.0
10.8
15
5.0
40.1
60
5.0
25.9
40
2.3
13.7
20
6.2
32.4
50
6.2
32.4
50
3.2
16.8
25
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
AWG 60 C
MAX WIRE
MIN
LENGTH
WIRE
14
75
12
80
12
80
14
55
10
90
12
65
14
100
8
100
10
85
14
100
6
100
10
75
14
100
8
95
8
95
12
100
7
457