CONTENTS
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
• ROOF CURB
• POSITIONING
• ROOF MOUNT
• FIELD POWER SUPPLY
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-21
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-24
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Book 1
4
Tab
5a 5a
Installation, Start-Up
and Service Instructions
Page
Catalog No. 535-00026
Printed in U.S.A.
50HJQ014-016
Single-Package Rooftop
Heat Pump Units
INSTALLATION
IMPORTANT: Units have high ambient operating lim-
its. If limits are exceeded, the unit will automatically
lock the compressor out of operation. Manual reset will
be required to restart the compressor.
Step 1 - Provide Unit Support
ROOF CURB - Assemble and install accessory roof curb in
accordance with instructions shipped with the curb. Accessory
roof curb and information required to field fabricate a roof curb
are shown in Fig. 1 and 2. Install insulation, cant strips, roofing,
and counter flashing as shown. Ductwork can be secured to
roof curb before unit is set in place. Horizontal adapter installa-
tion is shown in Fig. 3.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 1. Improperly applied
gasket can result in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain
to function properly. Unit leveling tolerances is ±
linear ft in any direction. Refer to Accessory Roof Curb Instal-
lation Instructions for additional information as required.
ALTERNATE UNIT SUPPORT - When the curb cannot be
used, support unit with sleepers using unit curb support area. If
sleepers cannot be used, support long sides of unit with a mini-
mum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 - Rig and Place Unit -
portation damage. File any claim with transportation agency.
Keep unit upright, and do not drop. Use spreader bars over unit
to prevent sling or cable damage. Rollers may be used to move
unit across a roof. Level by using unit frame as a reference;
1
leveling tolerance is ±
/
in. per linear ft in any direction.
16
See Fig. 1 for additional leveling tolerance information. Unit
weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 4. Refer to rigging instructions on unit.
POSITIONING - Provide clearance around and above unit
for airflow, safety, and service access (Fig. 5 and 6).
Do not install unit in an indoor location. Do not locate air in-
lets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
ROOF MOUNT - Check building codes for weight distribu-
tion requirements.
Form 50HJQ-8SI
Pg 1
1
/
in. per
16
Inspect unit for trans-
4-01
Replaces: 50HJQ-5SI