ELECTRICAL
UNIT
CHARACTERISTICS
50HS042,048 208/230-1-60, 208/230-3-60, 460-3-60 359 163 89/40 81/37 113/51 76/35
50HS060
208/230-1-60, 208/230-3-60, 460-3-60 373 170 92/42 85/39 116/53 80/36
REQ'D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side . . . . . . . . . . . . . . . . . . . 30 (762)
Control Box Access Side . . . . . . . . . . . . . . . . . . 30 (762)
(Except for NEC requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . 30 (762)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L — in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge, First 12 in. (305) of Supply Duct
NEC REQ'D CLEARANCES — in. (mm)
Between Units, Control Box Side . . . . . . . . . . . . . 42 (1067)
Unit and Ungrounded Surfaces, Control Box Side . . . . . .36 (914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . . . 42 (1067)
SIZES 042-060 WITHOUT BASE RAIL
UNIT WT
CORNER WT (Lb/Kg)
Lb
Kg
A
B
C
LEGEND
CG
— Center of Gravity
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required
. . . . . 1 (25)
CENTER OF GRAVITY (in./mm)
UNIT
D
X
50HS042,048
19.7/500
50HS060
19.7/499
NOTES:
1. Clearances must be maintained to pre-
vent recirculation of air from outdoor-fan
discharge.
2. Dimensions in ( ) are in mm.
Y
Z
20.5/522
15.0/381
20.6/523
15.0/381