Blowing-Out Process For The Pipe System; Checking The Airflow Sensor Calibration - Bosch FAS-420-TM Operation Manual

Aspirating smoke detector
Hide thumbs Also See for FAS-420-TM:
Table of Contents

Advertisement

90
en | Maintenance
7.7

Blowing-out Process for the Pipe System

Figure 7.4 Installing the three-way tap
The blast air supply (compressor or mobile blowing-out system) required for the blowing-out
process for the pipe system must be connected via the quick lock coupling fitting to the three-
way tap on the pipe system.
A check valve for relieving pressure from the pipe system must be fitted to the end of each
pipe branch. The check valve prevents damage to the air sampling openings and prevents dirt
deposits from being blown through the pipe system. To prevent aspiration reducing film
sheets in deep-freeze areas from tearing, it is advisable to use special deep-freeze aspiration
reductions.
The manual blowing-out process on the pipe system is carried out as follows (see Figure 7.4):
1.
2.
3.
7.8

Checking the Airflow Sensor Calibration

Check the airflow sensor value with the diagnostic software.
Functional principle
During initialization of the connected pipe system, the device saves the measured actual value
of the airflow as a target value via the integrated airflow monitoring. This nominal value then
serves as a reference value for the additional evaluation of a possible airflow malfunction.
F.01U.088.878 | 4.1 | 2010.11
1
C
B
A
C
1.
B
A
C
2.
B
A
C
3.
B
A
Position the tap lever so that the blast air and pipe system are connected (B-C
connection).
The connection to the FAS-420-TM must be blocked for blowing-out!
Manually blow out the pipe system for approximately 10 seconds.
Set the lever of the tap such that the device is not connected with the pipe system or
with the connection for the blast or compressed air supply. Wait approximately 20
seconds so that dust and dirt raised in the pipe system can settle and thus will not be
sucked through the aspirating smoke detector.
Reconnect the blown-out pipe system to the FAS-420-TM within a further 10 seconds by
switching over the tap accordingly (A-C connection).
Operation Guide
2
3
4
FAS-420-TM Aspirating Smoke Detector
1
Blast air/compressed air
connection
2
Pipe system connection
3
Aspirating smoke detector
connection
4
Air filter (optional)
Bosch Sicherheitssysteme GmbH