Calibrating The Airflow Sensor; Air-Pressure-Independent Calibration; Air-Pressure-Dependent Calibration - Bosch FAS-420-TM Operation Manual

Aspirating smoke detector
Hide thumbs Also See for FAS-420-TM:
Table of Contents

Advertisement

FAS-420-TM Aspirating Smoke Detector
Figure 6.1 Inserting the detector module into the housing base
6.3

Calibrating the Airflow Sensor

The airflow initialization of the FAS-420-TM is successfully completed if the status of the
temperature and the airflow stabilizes for a period of 2 minutes, i.e.:
The maximum operating period is 2 hours.
The airflow initialization is aborted immediately if one of the following errors occurs:
The calibration of the airflow sensor can be carried out independently of the air pressure or
depending on it.
To be able to judge the airflow sensor value correctly during start-up work, always adhere to
the type of calibration in the test log.
6.3.1

Air-Pressure-Independent Calibration

Calibration of the FAS-420-TM independently of the air pressure takes place automatically
each time the detector module is inserted into the housing base and the X4 jumper is
replugged, or via the FAS-ASD-DIAG Diagnostic Software.
During the teach-in phase, the alarm detection is fully functional. The operating display
flashes during this time and the airflow must not be influenced in any way. On completion of
initialization, the operating display is permanently lit and the airflow sensor has determined a
target value for the connected pipe system.
6.3.2

Air-Pressure-Dependent Calibration

A calibration of the airflow sensor that is dependent on the air pressure can only be carried
out using the FAS-ASD-DIAG Diagnostic Software. A barometer is required for this
(recommended: GPB 1300 digital precision pocket barometer from Greisinger electronic
GmbH).
The following steps are required:
1.
Bosch Sicherheitssysteme GmbH
X1
X2
X3
3
X4
The temperature fluctuates by less than 0.1 °C
The airflow is not fluctuating too heavily (temperature control)
The fan voltage can be set normally; fan and fan power pack working normally
Temperature measurement faulty
Airflow measurement faulty
Fan control faulty
In the "Settings" screen, press the bottom button [Set], so that you can change the
values in the diagnostic software.
1
Operation Guide
Commissioning | en
1 Housing Base
2 Detector module
3 Jumper X4
PIN 1-2 or PIN 2-3
2
F.01U.088.878 | 4.1 | 2010.11