Bosch FAS-420-TM Operation Manual page 35

Aspirating smoke detector
Hide thumbs Also See for FAS-420-TM:
Table of Contents

Advertisement

FAS-420-TM Aspirating Smoke Detector
Figure 3.2 Pipe configurations
Change of direction
Elbows and bends in the pipe system increase flow resistance. Therefore, they should only be
used where they cannot be avoided for structural engineering reasons.
Pipe elbow
Pipe bend
If elbows or bends are used, the maximum total length of the pipe system is reduced.
NOTICE!
It is preferable to use pipe bends rather than pipe elbows.
The detection time will be influenced significantly by too high a number of changes of
direction.
Testing
For critical applications, test the secure detection with activation attempts. Check also
whether there is airflow at the individual air sampling openings.
NOTICE!
In order to increase transport speed in critical application areas, the fan voltage can be
increased from 6.9 V to 9 V.
Bosch Sicherheitssysteme GmbH
U-pipe: pipe system that branches into two pipe branches.
M-pipe: pipe system that branches into three pipe branches.
Double U-pipe: pipe system that branches symmetrically into four pipe branches.
FAS / FCS
FAS / FCS
FAS / FCS
FAS / FCS
U/U
FAS / FCS
4U
Operation Guide
I
U
M
Corresponds to a straight pipe length of
1.5 m
0.3 m
Planning | en
I
I-pipe system
U
U-pipe system
M
M-pipe system
U/U
Double U-pipe system
F.01U.088.878 | 4.1 | 2010.11