Carrier WEATHERMASTER 50HJQ004-016 Product Data page 73

Single-package rooftop standard and high efficiency units 3 to 15 nominal tons
Hide thumbs Also See for WEATHERMASTER 50HJQ004-016:
Table of Contents

Advertisement

LEGEND
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
POT — Potentiometer
OAT — Outdoor-Air Temperature
RAT — Return-Air Temperature
NOTE 1
RUN
NOTE 3
50HJ540573
ACTUATOR
ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077
enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
→ ECONOMI$ER IV WIRING
NOTE:
Potentiometer Defaults Settings:
Power Exhaust
Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting
ECONOMI$ER2 WIRING
500 OHM
RESISTOR
-
+
OPTIONAL CO
2
SENSOR 4 - 20 mA
OUTPUT
NOTES:
1. 620 ohm, 1 watt 5% resister should be removed only when using differen-
tial enthalpy or dry bulb.
2. If a separate field-supplied 24v transformer is used for the IAQ sensor
power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
VIOLET
PINK
BLACK
4
3
5
BLUE
2
8
6
7
RED
1
10
11
9
WHITE
12
ECONOMISER2 PLUG
73