Performance data — 50HJQ (cont)
50HJQ008 (7
1
/
TONS) STANDARD MOTOR (BELT DRIVE)*
2
Airflow
0.2
(Cfm)
Rpm
Bhp
2250
511
0.53
2300
519
0.56
2400
534
0.61
2500
550
0.67
2550
558
0.71
2600
565
0.74
2700
581
0.81
2800
597
0.89
2900
613
0.97
3000
630
1.06
3100
646
1.15
3200
663
1.25
3300
679
1.35
3400
696
1.46
3500
713
1.58
3600
729
1.70
3700
746
1.83
3750
755
1.89
1
50HJQ008 (7
/
TONS) STANDARD MOTOR (BELT DRIVE)* (cont)
2
Airflow
1.2
(Cfm)
Rpm
Bhp
2250
832
1.71
2300
837
1.75
2400
847
1.83
2500
857
1.92
2550
862
1.97
2600
867
2.02
2700
878
2.12
2800
889
2.23
2900
900
2.34
3000
912
2.46
3100
923
2.58
3200
935
2.71
3300
947
2.84
3400
3500
3600
3700
3750
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 730 to 950 rpm. All other rpms require field-
supplied drive.
106
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
External Static Pressure (in. wg)
0.4
Watts
Rpm
Bhp
Watts
492
591
0.73
680
518
597
0.76
709
571
611
0.82
768
629
624
0.89
832
660
631
0.93
866
691
638
0.97
901
758
652
1.04
974
829
667
1.13
1051
905
681
1.22
1133
985
696
1.31
1220
1071
711
1.41
1313
1162
726
1.51
1411
1259
741
1.62
1514
1361
756
1.74
1623
1469
772
1.86
1737
1583
787
1.99
1857
1703
803
2.13
1985
1766
811
2.20
2051
External Static Pressure (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1592
882
1.99
1855
1630
886
2.03
1896
1710
896
2.12
1980
1794
905
2.22
2069
1838
910
2.27
2114
1884
915
2.32
2162
1978
926
2.42
2261
2077
936
2.54
2365
2181
947
2.65
2474
2290
958
2.78
2588
2406
969
2.90
2708
2526
2652
0.6
Rpm
Bhp
Watts
Rpm
660
0.95
885
722
666
0.98
916
727
678
1.05
982
739
690
1.13
1051
750
697
1.17
1088
756
703
1.21
1125
762
716
1.29
1204
774
729
1.38
1287
786
742
1.48
1376
799
756
1.58
1469
811
770
1.68
1568
824
784
1.79
1672
837
798
1.91
1781
851
812
2.03
1896
864
827
2.16
2017
878
841
2.30
2144
892
856
2.44
2277
906
864
2.52
2346
913
1.6
Rpm
Bhp
Watts
Rpm
928
2.29
2131
973
933
2.33
2174
977
942
2.43
2262
986
951
2.52
2355
995
956
2.58
2403
999
961
2.63
2453
971
2.74
2556
981
2.86
2664
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 113 for General Fan Performance Notes.
0.8
1.0
Bhp
Watts
Rpm
Bhp
1.19
1106
779
1.44
1.22
1140
784
1.48
1.30
1210
795
1.56
1.38
1285
805
1.64
1.42
1324
811
1.69
1.46
1365
816
1.73
1.55
1449
828
1.83
1.65
1538
839
1.93
1.75
1632
851
2.04
1.86
1731
863
2.15
1.97
1835
875
2.27
2.09
1944
888
2.39
2.21
2060
900
2.52
2.34
2181
913
2.66
2.48
2308
926
2.80
2.62
2441
2.77
2580
2.84
2653
1.8
2.0
Bhp
Watts
Rpm
Bhp
2.59
2420
2.64
2463
2.74
2556
2.84
2653
2.90
2704
Watts
1342
1378
1453
1533
1574
1617
1707
1801
1900
2004
2114
2229
2351
2478
2610
Watts

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents