50TFQ012 (10 TONS) — STANDARD MOTOR AND DRIVE*
Airflow
0.2
(Cfm)
Rpm
Bhp
3000
556
0.65
3100
569
0.70
3200
583
0.76
3300
597
0.83
3400
611
0.89
3500
625
0.96
3600
639
1.04
3700
654
1.11
3800
668
1.20
3900
683
1.28
4000
697
1.37
4100
712
1.47
4200
726
1.57
4300
741
1.67
4400
755
1.78
4500
770
1.89
4600
785
2.01
4700
800
2.14
4800
815
2.26
4900
829
2.40
5000
50TFQ012 (10 TONS) — STANDARD MOTOR AND DRIVE* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
3000
836
1.42
3100
846
1.50
3200
856
1.58
3300
866
1.67
3400
876
1.76
3500
886
1.86
3600
897
1.96
3700
907
2.06
3800
918
2.17
3900
929
2.28
4000
940
2.40
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
0.4
Watts
Rpm
Bhp
Watts
604
623
0.80
748
656
636
0.86
805
712
648
0.93
865
770
661
1.00
929
832
674
1.07
996
898
687
1.14
1066
967
700
1.22
1140
1040
713
1.31
1218
1116
726
1.39
1299
1197
739
1.48
1385
1281
753
1.58
1474
1370
766
1.68
1567
1462
780
1.79
1665
1559
794
1.89
1767
1660
807
2.01
1873
1766
821
2.13
1984
1876
835
2.25
2099
1991
849
2.38
2219
2111
2235
1.4
Watts
Rpm
Bhp
Watts
1322
881
1.57
1467
1398
890
1.66
1547
1477
899
1.75
1631
1559
909
1.84
1718
1645
919
1.94
1808
1734
929
2.04
1902
1827
939
2.14
2000
1924
949
2.25
2101
2025
959
2.37
2207
2130
2238
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
684
0.95
891
695
1.02
953
707
1.09
1018
718
1.17
1086
730
1.24
1158
742
1.32
1233
754
1.41
1312
767
1.50
1395
779
1.59
1481
792
1.69
1572
804
1.79
1666
817
1.89
1764
830
2.00
1866
843
2.12
1973
856
2.23
2084
869
2.36
2200
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
923
1.73
1613
932
1.82
1698
941
1.92
1786
950
2.01
1878
960
2.12
1972
969
2.22
2071
979
2.33
2173
Refer to page 30 General Fan Performance Notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
0.8
Rpm
Bhp
Watts
Rpm
738
1.11
1034
789
749
1.18
1100
799
760
1.26
1170
809
771
1.33
1244
820
782
1.42
1320
831
794
1.50
1400
841
805
1.59
1484
852
817
1.69
1571
863
828
1.78
1662
874
840
1.88
1758
886
852
1.99
1857
897
864
2.10
1960
909
876
2.22
2067
889
2.34
2179
1.8
Rpm
Bhp
Watts
Rpm
963
1.89
1761
1001
972
1.98
1849
1010
980
2.08
1942
1018
989
2.19
2038
1027
998
2.29
2137
1008
2.40
2240
1.0
Bhp
Watts
1.26
1177
1.34
1249
1.42
1323
1.50
1401
1.59
1483
1.68
1567
1.78
1656
1.87
1748
1.98
1844
2.08
1943
2.20
2048
2.31
2155
2.0
Bhp
Watts
2.05
1909
2.15
2002
2.25
2099
2.36
2199