Extended functions of group C

The functions of group C are used for configuring the programmable digital inputs and outputs.
Function
Display
Digital inputs 1, 2, 3, 4, and 5 can be assigned 15 different input functions. Every input can be assigned to any of the
15 input functions with the exception of the thermistor input function (parameter 19) which can only be assigned to
input 5. However, two different digital inputs can not be assigned the same input function.
The inputs can be programmed either as normally closed contacts or as normally open contacts (the only exception is
the digital input configured as RS, this input can not be programmed as normally closed contact).
Function of
C 01
digital input 1
Function of
C 02
digital input 2
Function of
C 03
digital input 3
Function of
C 04
digital input 4
Function of
C 05
digital input 5
Type of digital input 1
C 11
Type of digital input 2
C 12
Type of digital input 3
C 13
Type of digital input 4
C 14
Type of digital input 5
C 15
)
Function description / parameter setting range
*
Programmable digital inputs
The programmable digital inputs (control terminals 1 through 5) can be
assigned one of the following functions:
00: FW (start/stop forward run)
01: RV (start/stop reverse run)
02: CF1 (1. multistage frequency input)
03: CF2 (2. multistage frequency input)
04: CF3 (3. multistage frequency input)
05: CF4 (4. multistage frequency input)
06: JG (jogging run)
N
09: 2CH (2. acceleration/deceleration)
11: FRS (free run stop)
12: EXT (external trip)
13: USP (restart prevention function)
15: SFT (software lock)
16: AT (use input OI)
18: RS (reset)
19: PTC thermistor input (only digital input 5)
N Refer to C 01 for possible parameters
N Refer to C 01 for possible parameters
N Refer to C 01 for possible parameters
N Refer to C 01 for possible parameters
N
00: Normally open contact
N Refer to C 11 for possible parameters
N Refer to C 11 for possible parameters
N Refer to C 11 for possible parameters
N Refer to C 11 for possible parameters
8-13
Chapter 8 – Using the digital operator
01: Normally closed contact
Standard
setting
00
01
02
FE model
16
FU model
FE model
03
13
FU model
18
00
00
00
00
FE model
01
FU model
00