In order to test the inverter, follow the procedure described below:
1) Turn on power supply to the inverter. The power LED on the digital operator will light up.
2) Set function A 02 to 02.
3) Set function A 01 to 02. Set the corresponding frequency using function F 01.
4) After pressing the RUN key the motor starts to run and the the RUN lamp lights up.
5) The actual frequency can be monitored using function d 01.
6) You can stop the test run by pressing the STOP key.
CAUTION
After the test run has been completed, check the following items to ensure that the
motor will not be damaged:
Was the direction of the motor run correct? Was there any trip condition during
acceleration or deceleration? Were there any unusual motor sounds or vibrations?
When a trip occured during the test run due to overcurrent or overvoltage, increase
acceleration or deceleration time.