Hitachi L100 IP Series Instruction Manual page 66

Table of Contents

Advertisement

-
Inverter L 1 0 0
(400V series)
Protective structure (Note 1)
Overvoltage category
Maximum motor size (4P)
in kW (Note 2)
Maximum capacity
460V
in kVA
Input supply phase
Rated input voltage
Rated output voltage
(Note 3)
Rated input current in A
Rated output current in A
(Note 4b)
Output frequency range
Frequency accuracy
(at 25°C +/-10°C)
Frequency setting resolution
Voltage/frequency characterist.
Overload current capacity
Acceleration/deceleration time
Starting torque
Dynam. braking, feedback
to capacitor (Note 6)
DC injection braking
Dig. operator
Frequency
External
setting
signals
Forward /
Dig. operator
Reverse run
(Start/Stop) Ext. signals
Intelligent input terminals
programmable as
Intelligent output terminals
programmable as
Frequency and current
monitoring
Fault alarm contact
Other functions
Protection functions
Ambient temperature
Storage temperature and
humidity
Vibration
Installation location
External color
Options
Overall weight (app.) (Note 7)
007
015
022
HFE
HFE
HFE
007
015
022
HFU
HFU
HFU
0.75
1.5
2.2
1.9
3.0
4.3
007 ~ 075HF: 3 phase
380VAC –10% ~ 460VAC +10%
Three phase 380 ~ 460VAC
(Corresponds to input voltage)
3.3
5.0
7.0
2.5
3.8
5.5
0.5 ~ 360 Hz (Note 5)
Digital command: +/-0.01% of maximum frequency
Analog command: +/-0.2% of maximum frequency
Digital setting: 0.1 Hz Analog setting: maximum frequency /1000
Constant or reduced torque with any variable voltage/frequency
150% during 60 seconds (once per 10 minutes)
0.1 ~ 3000 s in selectable linear and non-linear mode
(second acceleration/deceleration usable)
100% ore more (when torque boost has been set)
ca. 100%
ca. 70%
Braking is on at the minimum frequency or less (minimum
frequency, braking time and braking force can be set)
Settings using keys
0-10VDC (input impedance 10k Ohm)
4-20mA (input impedance 250 Ohm)
Potentiometer 1k-2k Ohm, 1W
Via keys RUN (for start) and STOP/RESET (for stop)
(Default setting: forward run)
Intelligent input terminals configurable as FW and RV
FW: Forward run start/stop
CF1–CF4: Multistage speed
AT: Analog current input selection
FRS: Free run stop
USP: USP function
SFT: Software lock
FA1/FA2: Frequ. arrival signal RUN: Motor running signal
OL: Overload signal OD: PID deviation signal AL: Alarm signal
Connection of external analog meter (0-10VDC, max. 1mA) for
frequency or current; connection of external digital frequency meter
On when the inverter trips (1c contact)
Automatic voltage regulation,
analog gain/vias adjustment,
upper/lower limiter,
trip history monitoring,
PID control,
and many more
Overcurrent, overvoltage, undervoltage, electronic thermal,
temperature abnormality, ground fault upon starting, overload limit
-10 ~ 40°C
-25 ~ 70°C (during short term transportation period only)
20 ~ 90% RH (no dew condensation)
Max. 5.9m/s
1000m or less altitude indoors (IP54 or equivalent) (see chap.4)
Remote operator, copy unit, cable for digital operator,
reactor for improving power factor, noise filter, OPE-J
7.8
8.1
8.4
11-2
Chapter 11 – Technical specifications
040
055
HFE
HFE
040
055
HFU
HFU
IP54
III
4.0
5.5
6.8
10.3
50/60Hz +/-5%
11.0
16.5
8.6
13.0
ca. 20%
RV: Reverse run start/stop
JG: Jogging command
2CH: 2.Accel./decel. time
EXT: External trip
RS: Reset
PTC: Thermal protection
retry;
frequency jump,
output frequency display,
carrier frequency setting,
automatic torque boost,
2
(=0.6g) at 10-55Hz
Blue
8.5
9.4
075
HFE
075
HFU
7.5
12.7
20.0
16.0
9.6