11 11
Finishing
A. Mantel Projections
Figure 11.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of appliance mantels or
other combustible projections above the top front edge of
the appliance.
7
6
8-1/2
5
7-3/4
4
7
3
6-1/4
5-1/2
5
Figure 11.1 Clearances to Mantels or other Combustibles above
Appliance.
Top of
Appliance
A
1 in. (25 mm) min.
to perpendicular wall
B
3-1/2 in. (89 mm) min.
from fireplace opening
to perpendicular wall
Figure 11.2 Clearances to Perpendicular Wall
Mantel legs may be located adjacent to the side of the fi re-
box assembly. Combustible material may not cover the black
metal front of the fi replace.
24
30 in. minimum
16
15
14
14-1/2
13
13-3/4
12
13
11
12-1/4
10
11-1/2
9
10-3/4
8
10
9-1/4
Measured from top of hood (in inches)
Drywall
A
48 in.
(1219 mm)
max.
B
Mantel Leg or
Perpendicular Wall
Heatilator • Caliber BV Series • 4040-225 Rev J • 07/06
B. Facing Material
to ceiling
18
17
16
15-1/4
Figure 11.3 Noncombustible Facing Diagram
•
Black metal appliance front may be covered with non-
combustible material only.
•
Do NOT overlap combustible materials onto appliance
front.
•
Install combustible materials only up to specifi ed
clearances on top, front and sides.
•
Seal joints between the fi nished wall and appliance
top and sides using only a 300° F minimum sealant.
WARNING
Fire Risk
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
•
Modifying or covering grilles could cause
temperature rise and fi re hazard.
Finishing materials must not interfere with:
•
Air fl ow through grilles or louvers.
•
Operation of louvers or doors.
•
Access for service.
Finish wall material may be
combustible - Top and Sides
0 in.
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
WARNING
Fire Risk
Finish all edges and fronts to clearances and
specifi cations listed in manual.
0 in.
0 in.