Installation

Power and control wiring

Table 7 - Control interconnection
Outdoor unit
Number of wires x section area (mm²)
Including ground wire
TTK 512
TTK 518
TTK 524
TTK 530
TTK 536
TTK 048
TTK 060
TWK 512
TWK 518
TWK 524
TWK 530
TWK 536
TWK 048
TWK 060
Table 8 - Power supply outdoor unit (1)
Number of wires x section area (mm²)
Including ground wire
TTK/TWK 512
TTK/TWK 518
TTK/TWK 524
TTK/TWK 530
TTK/TWK 536
TTK/TWK 048
TTK/TWK 060
(1) Indoor and outdoor units are powered separately
(2) Number of wires and section area are given for a
maximum wire length of 50m. If the wire is longer
than 50m, these must be recalculated.
Table 9 - Power supply indoor unit (1)
Without electric heater
Number of wires x section area (mm²)
MCD/MWD 512
MCD/MWD 518
MCD/MWD 524
MCD/MWD 530
MCD/MWD 536
MCD/MWD 048
MCD/MWD 060
(1) Indoor and outdoor units are powered separately
(2) Number of wires and section area are given for a
maximum wire length of 50m. If the wire is longer
than 50m, these must be recalculated.
3 x 2.5
2 x 1.5
2 x 1.5
2 x 1.5
2 x 1.5
2 x 1.5
2 x 1.5
5 x 1.5
5 x 1.5
5 x 1.5
6 x 1.5
6 x 1.5
6 x 1.5
6 x 1.5
-
3 x 2.5
3 x 2.5
4 x 2.5
4 x 2.5
4 x 2.5
4 x 2.5
Number of wires x section area (mm²)
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
With electric heater
3 x 2.5 / 3 x 4
3 x 4
3 x 4
4 x 4
4 x 4
4 x 4
4 x 4
SS-SVX07B-E4