Installation Before starting Table 1 - Recommended sections of electric wires (power link) Creation of refrigerant lines Unit size Section Maximum fuse size To create the refrigerant lines you 2.5 mm² 16 aM will need refrigeration quality 518 - 524 2.5 mm²...
Installation Power and control wiring Table 7 - Control interconnection Outdoor unit Number of wires x section area (mm²) Including ground wire TTK 512 3 x 2.5 TTK 518 2 x 1.5 TTK 524 2 x 1.5 TTK 530 2 x 1.5 TTK 536 2 x 1.5 TTK 048...
Page 15
Installation Choice of installation Preparing the ceiling and installing the unit position Drill holes in the ceiling to fix the To ensure correct installation, the threaded rods according to the following points must be dimensions given the Dimensions considered. section. The angle brackets can also - The ceiling must be strong enough be used to space the drill holes.
Installation Refrigerant connections CAUTION! Passage of the tube and cable An insufficiently lubricated bundle It is possible to remove the electrical compressor may break down. Before drilling into the wall cabinet to facilitate access to the - make sure there are no pipes or refrigerant connection.
Page 17
Installation Screw/flare connections Unscrew the Flare nuts which are Brazed connections placed on the beginnings of the These lines will be created on the CAUTION! indoor unit lines. Put the Flare nut installation site. They will be When cutting, deburring and onto the tube.
Installation Condensate connections Electrical connections The unit must be perfectly level in All the wiring and earthing both directions. Connect the indoor arrangements must comply with unit's condensate tray to a local legislation. condensate drainage line. The unit is equipped with a 20 mm diameter WARNING! smooth tube connection.
Page 19
Installation Connecting the ducts Filtering Units can be equipped with Filtering the air is necessary to rectangular discharge and/or intake ensure the unit's correct operation. from the bottom or intake from the The unit is supplied with a filter. back ducts. Installing the wired WARNING! controller...
Operation Creating a vacuum Additional refrigerant R22 Refrigerant While the unit is operating, charge For this operation, use a pump charge the unit with gas through the service capable of creating a vacuum of Once the system has been vacuum Schraeder valve located at the 1 mm Hg (1.3mbar) or less.
Operation Fan speed Check the fan turns freely. Wired controller operation 10. Make sure the intake and Refer to the selection data to select Figure 12 - Wired controller discharge ducts are not blocked. the static pressure according to the 11.
Page 22
Operation Wireless controller Auto (optional) Clock The unit can be put into 5 different To set the clock: operation modes (FAN, COOL, DRY, HEAT and - Press the clock setting button To use the wireless controller, point AUTO). The cycling will be: (Figure 13, 18).
Maintenance WARNING! Handling the filter Disconnect the unit's power supply 1. To remove the filter, slightly push before servicing the unit. When the 4 clips down. servicing the units, make sure that 2. Remove the filter. the air passages through the coils 3.
Page 24
Maintenance Table 14 - Troubleshooting Symptoms Possible causes Checks Corrective action 1. Loose electrical connections. 1. Tighten the connections if necessary. A. Compressor or fan is not operating. 2. Check the fuses and wiring. 2. Replace the fuses if necessary. 1.
Page 25
Maintenance Symptoms Possible causes Checks Corrective action A. Control switch no longer responds to the 1. Check operation and connections of 1. Replace the control switch if it is defective. ambient temperature. the control switch. B. Loss of refrigerant fluid. 1.
Page 26
Trouble-shooting (electric heating only) Table 15 - Trouble-shooting (electric heating only) No heating. A. Incorrect control switch setting. 1. Check the thermostat's set points and 1. Change the settings. operation. B. Defective control switch. 1. Check operation and the signal to the 1.
SS-SVX07A-E4_0606 Stocking Location Europe Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication..