Ent Termination Requirements - Harman P35i Owner's Manual

Pellet/ biomass f ireplace insert/1-70-774195/1-70-774235
Table of Contents

Advertisement

5
V ent Information
A. V ent Termination R eq uirements
Sidewalk
WARNING: enting terminals must not be recessed into a
wall or siding.
NOTE: Only PL or L vent pipe wall pass-throughs and fire
stops should be used when venting through combustible
materials.
NOTE: Always take into consideration the affect the
prevailing wind direction or other wind currents will cause with
flyash and or smoke when placing the termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum of 12 .
B. The clearance to a window or door that may be opened
must be a minimum of 8 to the side and 8 below the
window door, and 12 above the window door.
(with outside air installed, 1 8 " to side and below)
C. A 12 clearance to a permanently closed window is
recommended to prevent condensation on the window.
. The vertical clearance to a ventilated soffit located above
the terminal within a horizontal distance of 2 feet ( 0 cm)
from the center-line of the terminal must be a minimum
of 18 .
E. The clearance to an unventilated soffit must be a minimum
of 12 .
. The clearance to an outside corner is 11 from center of
pipe.
G. The clearance to an inside corner is 12 .
H. A vent must not be installed within
a gas meter regulator assembly when measured from the
horizontal center-line of the regulator.
12
P e l l e t s o r C o r n /P e l l e t M i x t u r e O n l y
Chimney connector shall not pass through an attic or roof
Inside Corner
Detail
Fixed
Closed
Openable
V
=Vent Terminal
feet ( 0 cm) above
1
pace c
et r
m ar c ncea e
Openable
Fixed
Closed
A
=Air Supply Inlet
I. The clearance to service regulator vent outlet must be
a minimum of
. The clearance to a non-mechanical air supply inlet to
the building or the combustion air inlet to any other
appliance must be a minimum of 8 .
. The clearance to a mechanical air supply inlet must be
a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
1
driveway located on public property must be a minimum
of 7 feet.
. The clearance under a veranda, porch, deck or balcony
1
must be a minimum of 12 inches.
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is
center of the outlet or cap. This
grade or a minimum of 7 feet below the outlet.
Certain Canadian and or Local codes or regulations may
1
require different clearances.
A vent shall not terminate directly above a side-walk or
2
paved driveway which is located between two single family
dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is fully
3
open on a minimum of 2 sides beneath the floor.
NOTE: In Canada, where passage through a wall or
partition of combustible construction is desired, the
installation shall conform to CAN/ CSA-B3 6 5 .
- 0-775R1
08 1
P3 5 i F ireplace Insert
pace
r a
Porch or
Openable
=Area where termination is mot permitted
feet.
1
1
1 ,2
1 ,3
as measured from the
r r ce n
Deck
or Fixed
1
(B. also)
radius continues to
S a v e
T h e s e
I n s t r u c t i o n s

Hide quick links: