Omron Powli BY35S Instruction Manual page 37

Table of Contents

Advertisement

4
.UPS functions
2-2 Settings
The UPS operation mode can be set if the power switch is turned ON while the beeper stop /test
switch is pressed.
Note: While in setting mode, output from the power supply output is OFF even if the power
switch is ON.
(1) When the beeper stop/test switch is briefl y pressed (for less than 1 second), the next item is
displayed.
(2) The unit enters the "individual item setting mode" when the beeper stop/test switch is
pressed and held (for more than 1 second).
(3) When the power switch is turned OFF, the setting mode quits and the unit enters power
switch OFF status (status
Normal status
A
Setting mode
Cold start
ON/OFF setting
D
D
Input power
sensitivity setting
*1 Displays the current setting value.
*2 The setting applied to BY35S/BY50S/BY80S/BY120S is the same as the standard voltage sensitivity setting.
26
Cold start ON/OFF setting
Input power sensitivity setting
).
There is AC input
Power switch "OFF" (Status No. 2)
B
OFF
C *1
C
ON
C *1
D
C
D
Beeper stop/test
Power suppply ON/OFF
A
Turn ON the power switch while the beep stop/test switch is pressed.
B
Turn OFF the power switch.
C
Press and hold the beep stop/test switch (for more than 3 seconds).
D
Press the beep stop/test switch (for less than 3 seconds).
Cold start OFF mode (Factory-shipped setting)
D
D
Cold start ON mode
Standard voltage sensitivity setting (at shipment)
Low voltage sensitivity *2
High voltage sensitivity
D