Volt Humidifier; Gas Supply And Piping; General; Gas Piping Connections - Goodman GMV95 Installation Instructions Manual

Two-stage gas-fired warm air furnace
Table of Contents

Advertisement

CONTROL MODULE
CONTROL MODULE
OPTIONAL ACCESSORIES
OPTIONAL ACCESSORIES
Accessories Wiring
If it is necessary for the installer to supply additional line voltage
wiring to the inside of the furnace, the wiring must conform to all
local codes, and have a minimum temperature rating of 105°C. All
line voltage wire splices must be made inside the furnace junction
box.
The integrated control module humidifier terminals (HUM) are en-
ergized with 115 volts whenever the induced draft blower is ener-
gized. The integrated control module electronic air cleaner termi-
nals (EAC) are energized with 115 volts whenever the circulator
blower is energized.
24 V
H
OLT
UMIDIFIER
A 5" long brown wire in the wire harness at the low fire pressure
provides 24 VAC humidifier control. This wire is powered any time
the pressure switch is closed. To connect 24 VAC HUM, connect
the 24 VAC line of the humidifier to the 5" brown wire. The connec-
tion can be made by either stripping the wire and using a wire nut
or by using a field supplied quick connect terminal. The wiring
must conform to all local and national codes. Connect the COM
side of the humidifier to the B/C terminal on the furnace control
board (or to the COM side of the 24 VAC transformer). Do not
connect 115V humidifier to these terminals.
XII. GAS SUPPLY AND PIPING
G
ENERAL
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE
I
NLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES
.
OPERATING
Inlet gas supply pressures must be maintained within the ranges
specified below. The supply pressure must be constant and avail-
able with all other household gas fired appliances operating. The
minimum gas supply pressure must be maintained to prevent
unreliable ignition. The maximum must not be exceeded to pre-
vent unit overfiring.
Inlet Gas Supply Pressure
Natural Gas
Minimum:5.0" W.C. Maximum :10.0" W.C.
Propane Gas
Minimum:11.0" W.C. Maximum :13.0" W.C.
12 CIRCUIT
12 CIRCUIT
CONNECTOR
CONNECTOR
INTEGRATED
INTEGRATED
HUMIDIFIER
HUMIDIFIER
ELECTRONIC
ELECTRONIC
AIR CLEANER
AIR CLEANER
CAUTION
H
A
D
IGH
LTITUDE
When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied. This is required due to the
natural reduction in the density of both the gas fuel and combus-
tion air as altitude increases. The kit will provide the proper design
certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation alti-
tude and usage of either natural or propane gas. Contact your
distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer's high altitude (Natural, propane gas,
and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pressure to a
lower pressure than specified on the furnace rating plate. The
combination of the lower air density and a lower manifold pressure
will prohibit the burner orifice from drawing the proper amount of
air into the burner. This may cause incomplete combustion, flash-
back, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude. If the gas is artifi-
cially derated, the appropriate orifice size must be determined
based upon the BTU/ft
Refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and
information provided by the gas supplier to determine the proper
orifice size.
A different pressure switch may be required at high altitude regard-
less of the BTU/ft
3
for a tabular listing of appropriate altitude ranges and correspond-
ing manufacturer's pressure switch kits.
P
G
C
ROPANE
AS
ONVERSION
P
OSSIBLE PROPERTY DAMAGE
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
FURNACE OPERATION
A QUALIFIED INSTALLER OR SERVICE AGENCY
This unit is configured for natural gas.
manufacturer's propane gas conversion kit, must be applied for
propane gas installations. Refer to the Section VIII, Propane Gas
/ High Altitude Installations section for details.
G
V
AS
ALVE
This unit is equipped with a 24 volt gas valve controlled during
furnace operation by the integrated control module. As shipped,
the valve is configured for natural gas. The valve is field convertible
for use with propane gas by replacing the regulator spring with a
propane gas spring from an appropriate manufacturer's propane
gas conversion kit. Taps for measuring the gas supply pressure
and manifold pressure are provided on the valve.
,
THE
The gas valve has a manual ON/OFF control located on the valve
itself. This control may be set only to the "ON" or "OFF" position.
Refer to the lighting instructions label or Section XIV, Startup Pro-
cedure & Adjustment for use of this control during start up and shut
down periods.
G
P
C
AS
IPING
ONNECTIONS
G
ENERAL
T
O AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT
DAMAGE DUE TO UNDERFIRING OR EQUIPMENT
SIZE OF NATURAL
PIPE FROM THE METER
24
ERATE
3
content of the derated gas and the altitude.
content of the fuel used. Contact your distributor
WARNING
,
PERSONAL INJURY OR DEATH MAY
. A
LL CONVERSIONS MUST BE PERFORMED BY
.
CAUTION
,
/
PROPANE GAS PIPING NEEDED WHEN RUNNING
/
.
TANK TO THE FURNACE
. T
HE
The appropriate
USE THE PROPER

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gcv9

Table of Contents