Volt Humidifier; Gas Supply And Piping; High Altitude Derate; Propane Gas Conversion - Goodman *MVM96 Installation Instructions Manual

Modulating gas furnace
Hide thumbs Also See for *MVM96:
Table of Contents

Advertisement

call for humidity. The integrated control module electronic air
cleaner terminals (EAC) are energized with 115 volts whenever
the circulator blower is energized.
24 V
H
OLT
UMIDIFIER
A 24 volt humidifier can be powered by feeding one of the
HUM terminals with a field installed wire from the R terminal
or by connecting to the NO side of the low fire pressure
switch.
G
S
P
AS
UPPLY AND
IPING
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
T
 
 
 
O
PREVENT
UNRELIABLE
OPERATION
 
 
 
 
INLET
GAS
SUPPLY
PRESSURE
MUST
 
 
 
 
RATING
PLATE
WITH
ALL
OTHER
.
OPERATING
Inlet gas supply pressures must be maintained within the ranges
specified in the following table. The supply pressure must be
constant and available with all other household gas fired appli-
ances operating. The minimum gas supply pressure must be
maintained to prevent unreliable ignition. The maximum must not
be exceeded to prevent unit overfiring.
Inlet Gas Supply Pressure
Natural Gas
Minimum:
Propane Gas
Minimum: 11.0" w.c.
H
A
D
IGH
LTITUDE
ERATE
In some areas the gas supplier may artificially derate the gas in
an effort to compensate for the effects of altitude. If the gas is
artificially derated, the appropriate orifice size must be deter-
mined based upon the BTU/ft
altitude. Refer to the National Fuel Gas Code, NFPA 54/ANSI
Z223.1 or CAN/CSA B149.1 in Canada, and information pro-
vided by the gas supplier to determine the proper orifice size.
P
G
C
ROPANE
AS
ONVERSION
P
 
 
OSSIBLE
PROPERTY
DAMAGE
 
 
 
 
OCCUR
IF
THE
CORRECT
CONVERSION
 
 
 
 
APPROPRIATE
KITS
MUST
BE
APPLIED
 
. A
 
FURNACE
OPERATION
LL
CONVERSIONS
 
 
 
QUALIFIED
INSTALLER
OR
SERVICE
As shipped, this unit is configured for natural gas. The appropri-
ate manufacturer's propane gas conversion kit, must be applied
for propane gas installations. Refer to the Propane Gas and/or
High Altitude Installations for details.
Consult the furnace Specification Sheet for a listing of appro-
priate kits. The indicated kits must be used to insure safe and
proper furnace operation. All conversions must be performed by
a qualified installer, or service agency.
CAUTION
 
 
 
OR
EQUIPMENT
DAMAGE
 
 
 
 
 
 
BE
AS
SPECIFIED
ON
THE
UNIT
 
 
 
 
HOUSEHOLD
GAS
FIRED
APPLIANCES
4.5" w.c.
Maximum: 10.0" w.c.
Maximum: 13.0" w.c.
3
content of the derated gas and the
WARNING
 
 
 
 
PERSONAL
INJURY
OR
DEATH
MAY
 
 
 
 
. T
KITS
ARE
NOT
INSTALLED
 
 
 
 
 
TO
ENSURE
SAFE
AND
PROPER
 
 
 
MUST
BE
PERFORMED
 
.
AGENCY
G
V
AS
ALVE
This unit is equipped with a 24 volt gas valve which modulates by
pneumatic linkage to the combustion air blower. Taps for mea-
suring the gas supply pressure and manifold pressure are provided
on the valve. This is a non-convertible, non-adjustable gas valve
equipped for natural gas.
The gas valve has a manual ON/OFF control located on the valve
itself. This control may be set only to the "ON" or "OFF" position.
Refer to the lighting instructions label or the Startup Procedure &
Adjustment section of this manual for use of this control during
start up and shut down periods.
G
P
C
AS
IPING
T
 
 
O
AVOID
POSSIBLE
 
DAMAGE
DUE
 
THE
 
/
OF
NATURAL
 
 
/
THE
METER
TANK
 
The gas piping supplying the furnace must be properly sized based
on the gas flow required, specific gravity of the gas, and length of
the run. The gas line installation must comply with local codes, or
in their absence, with the latest edition of the National Fuel Gas
Code, NFPA 54/ANSI Z223.1 or CAN/CSA B149.1 in Canada.
Natural Gas Capacity of Pipe In Cubic Feet of Gas Per Hour (CFH)
Nominal
Actual ID:
Length (ft)
10
20
30
40
50
60
70
80
90
100
125
150
175
200
250
This chart refers to natural gas with an inlet pressure of less than 2 psi and a pressure
 
drop of 0.5" W.C. Specific gravity is 0.60.
 
HE
 
CFH =
 
 
 
BY
A
To connect the furnace to the building's gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve. In some cases, the
installer may also need to supply a transition piece from 1/2" pipe
to a larger pipe size.
The following stipulations apply when connecting gas piping. Re-
fer to Gas Piping Connections figure for typical gas line connec-
tions to the furnace.
31
ONNECTIONS
WARNING
 
 
UNSATISFACTORY
OPERATION
 
 
 
 
TO
UNDERFIRING
OR
EQUIPMENT
 
 
 
 
PROPANE
GAS
PIPING
NEEDED
WHEN
 
 
 
.
TO
THE
FURNACE
Pipe Size (in.)
½
¾
1
0.622
0.824
1.049
1.380
Capacity in Cubic Feet of Gas per Hour
170
360
678
1390
118
247
466
957
95
199
374
768
81
170
320
657
72
151
284
583
65
1370
257
528
60
126
237
486
56
117
220
452
52
110
207
424
50
104
195
400
44
92
173
355
40
83
157
322
37
77
144
296
34
71
134
275
30
63
119
244
BTUH Furnace Input
Heating Valve of Gas (BTU/Cubic Foot)
 
 
 
OF
EQUIPMENT
 
 
 
 
USE
THE
PROPER
SIZE
 
 
 
 
RUNNING
PIPE
FROM
2
1.610
2.067
2.469
2090
4020
6400
1430
2760
4400
1150
2220
3530
985
1900
3020
873
1680
2680
791
1520
2430
728
1400
2230
677
1300
2080
635
1220
1950
600
1160
1840
532
1020
1630
482
928
1480
443
854
1360
412
794
1270
366
704
1120

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents