030Error - Navien NCB-180 Service Manual

Condensing boiler
Table of Contents

Advertisement

5.2.5 030Error

Error occurrence conditions and check items
Error
If the overheat controller on the top of the exhaust duct is initiated, the system displays the heat exchanger
bimetal overheat message 030E (cleared manually) on the front panel.
The boiler switches into Lock-Out, and performs post-purge continuously and operates the pump.
Overheating controller operates when the temperature exceeds 230°F (110°C) for 10 minutes or over.
E030
1. When the controller detects the exceeding temperature of 230°F (110°C) for 10 minutes or over, "E030"
Exhaust gas
error code will display and perform post-purge.
temperature error
2. When the controller detects the exceeding temperature of 140°F (60°C) while performing post-purge.
3. When the controller detects the exceeding temperature of 230°F (110°C) for 10 seconds or over three
times or more after the error is automatically cleared.
1. Check if the overheat controller operates normally.
Check items
2. Check if the PCB works properly.
92
NCB Service Manual
Manually cleared.
Is exhaust thermistor
normally operating?
Yes
Check the heat exchanger
Check for leakage in the
combustion chamber
Flush heat exchanger
Description
Automatically cleared.
Manually cleared.
NO
Check the exhaust thermistor
Check the resistance between #9 and #10 of CN 13:
short-circuit (check page 51 for Wiring Diagram)
Version 1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ncb-210Ncb-240

Table of Contents