Navien NCB-180 Service Manual page 24

Condensing boiler
Table of Contents

Advertisement

Setting the Front Panel DIP Switches
Before change the settings, lift the rubber cover to access the front panel DIP switches.
 Set of DIP Switches 1 (Set of 10)
The DIP SW 1 on the front panel configures the temperature ufnit, well pump, and high altitude settings.
SW1 NO.
Application
1
Reserve
Temperature
2
Unit
3
Well Pump
4 & 5
High Altitude
6
Reserve
7
Reserve
8
Reserve
9
Reserve
10
Reserve
S/W 1
Setting
℃ (Celsius)
℉ (Fahrenheit)
Well Pump ON
Well Pump OFF
0-1,999 ft (0-609 m)
2,000-5,399 ft (610-1,645 m)
5,400-7,699 ft (1,646-2,346 m)
7,700-10,100 ft (2,347-3,078
m)
S/W 2
2-ON
2-OFF
3-ON
Well Pump Mode
These settings are to be used with well system
3-OFF
when an external pump is wired to the boiler.
4-OFF, 5-OFF
High Altitude
Above 2,000 ft (610 m), the boiler will de-rate
4-ON, 5-OFF
by 4% for each 1,000 ft (305 m) of altitude gain.
This boiler may be installed at elevations up to
4-OFF, 5-ON
10,100 ft (3,078 m) for use with Natural Gas
and 4,500 ft (1,370 m) for use with Propane. To
use the boiler at a specific altitude, the DIP
4-ON, 5-ON
switches should be set as described above.
Remarks