Failure
Cause
mode
Main gas valve
Ignition
failure
84
NCB Service Manual
1. Check the primary/secondary power supply to the main gas valve.
Check, with a multi-meter, if the input power is DC 22-24 V.
2. Replace the PCB if power is not supplied.
3. If power supply is normal, check if the coil is open.
Check the resistance. (refer to page 125)
4. Check if the solenoid valve works properly.
Feel or hear a click.
PIN No.
Check if the coil is open (Proper resistance range : 100~1,000 Ω)
Check the voltage of the solenoid valve / White-Yellow, White-Red
Check method