Checking The Ignition Device; Checking The Flue System; Checking The Condensate Drain Pipe; Instructing The User - Biasi RIVA ADVANCE HE M110.24SM User Manual And Installation Instructions

Wall hung, fan flue, room sealed, high efficiency gas boiler
Table of Contents

Advertisement

Commissioning
In any case, the boiler automatically resets to
its normal operation after 10 minutes.
After setting the coefficient K, position the knob 8
as shown in Fig. 7.11 in order to obtain the c.h.
flow temperature accordingly with the chart of
Fig. 7.7.
8
Fig. 7.11
However, the setting point of the c.h. flow tempera-
ture can be manually increased or decreased
within a range of ±15 ûC by turning the knob 8.
The effect of the knob 8 for a coefficient K set to 1,5
is illustrated in Fig. 7.12.
C.h. flow temperature ûC
80
+ 15ûC
70
60
50
K=1,5
40
30
--- 15ûC
20
20
15
10
5
Fig. 7.12
7.10

Checking the ignition device

With the burner on high flame close the gas cock.
After four ignition attempts (within about four min-
utes), the lock--- out signal lamp 6 (Fig. 1.3 on
page 2) must appear.
To reset the boiler press and release the boiler
reset button 7 (Fig. 1.3 on page 2).
7.11

Checking the flue system

The flue system should be visually checked for
soundness. Check all clamps, gaskets and fixing
are secure and tight.
34
0
--- 5 --- 10 --- 15 --- 20 --- 25
External temperature ûC
Ensure that the flue terminal is sited correctly in ac-
cordance with the flue fitting instructions and
Fig. 5.1 on page 20 of this manual.
To carry out a combustion check refer to the in-
structions given in the section 8.5 of this manual.
Reference figures are given in the sections 4.3 or
4.4 of this manual (Flue gas figures).
7.12
Checking the condensate
drain pipe
Check the soundness and integrity of the conden-
sate drain pipe.
Verify the cleanness and correct filling of the con-
densate traps.
7.13

Instructing the user

Hand over this combined User & Installation man-
ual and the Service manual to the end user and ex-
plain how to use the unit in both c.h. and d.h.w.
modes.
Take the User step by step through the lighting in-
structions.
Show the User how to switch off the appliance
quickly and indicate the position of the electric
supply isolator.
Explain the proper use and adjustment of all sys-
tem controls; this will ensure the greatest possible
fuel economy.
Explain the function and use of the function selec-
tor.
Explain and demonstrate the function of time and
temperature controls (if fitted).
Explain how to turn off the appliance for both short
and long periods and advise on the precautions
necessary to prevent damage should the
appliance be inoperative when freezing condi-
tions may occur.
Fill in the details required on the Boiler Guarantee
Certificate and hand to the User advising them to
return the correct section for boiler Guarantee reg-
istration.
Finally, advise the User that, for continued safe
and efficient operation, the appliance must be ser-
viced by a competent person at least once a year.