Checking The Pressurisation In The Expansion Vessel; Cleaning The Burner; Checking The Flue; Drain Pipe Inspection - Biasi RIVA ADVANCE HE M110.24SM User Manual And Installation Instructions

Wall hung, fan flue, room sealed, high efficiency gas boiler
Table of Contents

Advertisement

J
Fig. 8.6 (right side of the fan)
9 Disconnect the connector of the fan M by pres-
sing the plastic hook N placed on the rear side
of the connector (Fig. 8.7).
N
Fig. 8.7 (rear view of the fan)
If you notice dirt on the coil of the condensing heat
exchanger (19 on page 12) brush out it with a
bristle paintbrush and remove the dust with a
hoover.
Reassemble the parts carrying out the removal
operations in reverse order.
8.7
Checking the pressurisation
in the expansion vessel
Empty the central heating system as described in
section 8.4 of this chapter and check that the pres-
sure in the expansion vessel is not less than 1 bar.
See also section 4.6 page 18 of this manual.
If the pressure is lower, take steps to correct the
pressure level.
G
8.8
K
The burner (38 on page 12) does not need special
maintenance, but it is sufficient to dust it with a
bristle paintbrush.
I
To reach the burner do the operations described
in the section 8.6 of this manual
8.9
H
Have the integrity of the flue outlet pipe (47 on
page 13) air intake pipe (48 on page 13), checked
periodically, at least once a year.
For all the above maintenance operations it is ad-
visable to call an approved Service Engineer.
8.10
Check the soundness and integrity of the conden-
sate drain pipe.
Verify the cleanness and correct filling of the con-
densate traps.
M
8.11
Visually inspect all water joints, seals and connec-
tions for any evidence of leakage and retighten,
grease or replace them as necessary.
8.12
Check appliance for gas soundness. Recheck op-
erational pressures as described in section 7.7
page 32 of this manual.
8.13
Where chemical products are used the level of
water treatment should be checked on an annual
basis and re treated after full or partial drain down.
A conductivity meter can be used to check the cor-
rect concentration of inhibitor in the heating water.

Cleaning the burner

Checking the flue

Drain pipe inspection

Visual inspection of
appliance

Gas pressures and soundness

Water inhibitor concentration

Maintenance