C.
FLUE SYSTEM APPROVALS AND
INSTALLATIONS
MODEL
FLUE TERMINATION APPROV-
ALS
6000TRSI-AUC
DVP-TRAP2, DVP-TVHW
TABLE 1
This model is approved to use DVP-Series flue pipe
components. A DVP-TRAP2 Termination Cap must
be used to terminate flue systems in a horizontal
position. A DVP-TVHW vertical Termination Cap must
be used to terminate flue systems in a vertical posi-
tion.
Figures 1.7 through 1.14 show the flue systems ap-
proved for these models. Approved flue system com-
ponents are labeled for identification. NO OTHER
FLUE SYSTEMS OR COMPONENTS MAY BE
USED. Detailed installation instructions are included
with each flue termination kit and should be used in
conjunction with this manual.
WARNING: THIS GAS APPLIANCE AND FLUE AS-
SEMBLY MUST BE FLUED DIRECTLY TO THE
OUTSIDE AND MUST NEVER BE ATTACHED TO A
CHIMNEY SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE. EACH GAS APPLIANCE
MUST USE A SEPARATE FLUE SYSTEM-COMMON
FLUE SYSTEMS ARE PROHIBITED.
CAUTION: UNDER NO CONDITION SHOULD COM-
BUSTIBLE MATERIAL BE CLOSER THAN 3
INCHES (2 1/2 INCHES AT WALL FIRESTOPS)
FROM THE TOP OF THE 8 INCH PIPE OR 1- INCH
TO THE SIDES AND THE BOTTOM FOR HORIZON-
TAL SECTIONS OF THIS FLUE SYSTEM. VERTI-
CAL SECTIONS OF THIS SYSTEM REQUIRE A
MINIMUM OF 1 INCH CLEARANCE TO COMBUS-
TIBLE MATERIALS ALL AROUND THE 8 INCH
PIPE.
For alternative installations, other than depicted, con-
tact your dealer for further information.
Refer to Figure 1.4 for required clearances to flue
terminals.
8
Heat & Glo • 6000TRSI-AUC • 2078-900 Rev.C • 7/06
VERTICAL FLUE RESTRICTOR
If the heater installation requires a vertical flue ex-
ceeding 4.5m above the unit with no horizontal flue
or elbows a vertical flue restrictor must be installed
(see Figure 1.5).
RESTRICTOR
PLATE
FIGURE 1.5
STRAIGHT UP VERTICAL FLUE SYSTEM
Figure 1.6 shows straight up vertical flue system ap-
proved for use on this model.
CAP
V
MAX. RUN
36 FT.
(10.97m)
FIGURE 1.6