Troubleshooting; Viii. Troubleshooting; Heating System - Thermo Pride OPA Installation And Service Manual

Outdoor combination oil-fired furnace and air conditioning unit
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
: Power must be disconnected before servicing.
Refer to the appendices of this manual for an electrical schematic, a connection
diagram, flowcharts to assist in troubleshooting, product specifications, and a
replacement parts list follow for this appliance.
A. Heating System:
Qualified HVAC and cooling contractors must perform all service.
NOTICE: Before troubleshooting, familiarize yourself with the Initial Startup,
Checkout Procedure, and Heating System Troubleshooting Flowchart.
To assist in troubleshooting the heating section of this appliance, it is equipped with
an integrated safety and ignition control with diagnostics. These diagnostics include
an indicator light that relays the operational status of the control and can help in
diagnosing the condition of the flame sensor.
Diagnostic Features
The Honeywell brand model R7184P (or alternate R7997D) safety and ignition
control module used on this unit continuously monitors the operation of the heating
system. If an abnormal condition occurs, the LED light on the control will rapidly
flash indicating the operational status of the unit. In event this control
malfunctions, the entire control should be replaced. It is not field-repairable.
In the event of an operational failure of the burner system, the rate of flashes, if any,
of the ignition control module LED should be noted, before turning off power to the
unit. Otherwise, power to the heating section will be interrupted and the control LED
will not furnish the diagnostic flashing. It may be necessary to restart the furnace and
have the failure occur again. For the model R7184P, under normal operating
conditions, the LED will be continuously lit while the burner is operating. For
the model R7997D, the LED will be continuously flash at a low rate
(approximately 2 seconds "on", 2 seconds "off") while the burner is operating.
If either control has sensed a flame failure, which was uncorrected by initiating
another trial-for-ignition, the control will cease ignition trials and shutdown the
burner, or "lockout". The LED will continuously flash at a high rate (approximately
1/4-second "on"; 1/4 second "off", for the model R7184P, or approximately 1/2-
second "on"; 1/2 second "off", for the model R7997P) during the lockout mode. To
initiate another trial-for-ignition, it is necessary to manually depress the reset button
on the control module.
I
: If the appliance fails to relight after resetting the primary control twice
contact a qualified service company. DO NOT continue to reset primary control.
VIII.

TROUBLESHOOTING

59