Troubleshooting Flowchart - Thermo Pride OME-72D36 Installation And Service Manual

Oil-fired furnace down flow & direct vent (sealed combustion)
Hide thumbs Also See for OME-72D36:
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
Set thermostat subbase to "HEAT"
Does thermostat make contact?
Yes
Is room temperature above
Does a "call for
No
heat" initiate an
Is the power switch "off"?
ignition cycle?
across lines L1 & L2?
Yes
No
Is room temperature
above 90 deg. F?
No
thermostat setting?
No
Replace thermostat
No
Is there 120 VAC
Yes
Is the oil primary control
receiving 120 VAC?
Yes

TROUBLESHOOTING FLOWCHART

Note: Check diagnostic code through view port
prior to removing doors.
Yes
Wait for room air to cool.
Yes
Turn thermostat setting
above room temp.
Yes
Turn power
switch "on".
No
Check input power. Reset circiut
breaker, or replace blown fuse in
disconnected switch.
No
Have either of the
high limit thermostats
activated?
With power on,measure
voltage across the aux.
high limit thermostat N.C.
contact to L2. If not 120 VAC,
replace aux. high limit
thermostat. Else,replace
high limit thermostat.
34
Wait for furnace to cool.
Look for cause(s) of high
Yes
limit activation,eg. low
airflow, over-firing,
blocked flue,etc..
Correct any
abnormal conditions.
No