Thermo Pride OPA Installation And Service Manual

Outdoor combination oil-fired furnace and air conditioning unit
Table of Contents

Advertisement

OUTDOOR COMBINATION OIL-FIRED
FURNACE AND AIR CONDITIONING UNIT
INSTALLATION AND SERVICE MANUAL
: If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage, personal
injury, or loss of life.
− Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
− WHAT TO DO IF YOU FIND AN OIL LEAK:
• Do not try to light any appliance.
• Immediately call your oil supplier.
• If you cannot reach your oil supplier, call the fire department.
− Installation and service must be performed by a qualified installer, service
agency or the oil supplier. (These entities are referred to in these instructions
as a qualified heating contractor).
Please read these instructions prior to installation, initial firing, and before
performing any service or maintenance.
These instructions must be retained by the homeowner for future reference by
qualified heating contractor.
MO-424
ECN 4650-MA
MODEL OPA
Thermo Products, LLC
PO Box 217
North Judson, IN 46366
Phone: (574) 896-2133
Made In USA

Advertisement

Table of Contents
loading

Summary of Contents for Thermo Pride OPA

  • Page 1 OUTDOOR COMBINATION OIL-FIRED FURNACE AND AIR CONDITIONING UNIT MODEL OPA INSTALLATION AND SERVICE MANUAL : If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
  • Page 2: Table Of Contents

    H. Airflow Requirements and Sizing of Ductwork ......…….. 19 I. Air Filters ..................…….. 23 1. Filter Installation ..............…….. 23 2. Use of non-Thermo Pride Filters or Retention Means ....……. 23 J. Electrical Wiring ................……. 24 1. Electronic Air Cleaner (EAC) and Humidifier Installation ..…… 26 2.
  • Page 3 APPENDIX D: SEQUENCE OF OPERATIONS ........….. 76 XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS ......….. 78 APPENDIX F: SPECIFICATION SHEETS ..........…. 86 XVI. APPENDIX G: REPLACEMENT PARTS ..........….. 87 XVII. APPENDIX H: OPA HEATING AND COOLING TEST FORM ....…. 89 WARRANTY …………………………………………………………………….. 90...
  • Page 4: Safety Information

    All installations and services must be performed by qualified service personnel. I. SAFETY INFORMATION This page and the following page contain reproductions of the various instructions and warning labels placed on the Thermo Pride gas-fired appliances. Please read and comply with the contents of these labels.
  • Page 5 All installations and services must be performed by qualified service personnel.
  • Page 6 All installations and services must be performed by qualified service personnel. The following warnings and cautions are found throughout the Thermo Pride Model OPA Installation and Service Manual. Please read and comply with the statements below. : IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
  • Page 7 All installations and services must be performed by qualified service personnel. : Waterproof type connectors must be used when connecting electrical power and control wiring to the unit to prevent moisture from being drawn into the unit during operation. : Refrigerant is under pressure. Guard against refrigerant spraying into the face or on skin.
  • Page 8 All installations and services must be performed by qualified service personnel. : For initial start-up of the appliance after installation, it may be necessary to purge the air out of the oil line. A qualified heating contractor should do this. : If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 9 All installations and services must be performed by qualified service personnel. : Carefully read and thoroughly understand the following guidelines and warnings before continuing with the installation of this appliance. Failure to follow these guidelines can cause improper and unsafe operation of this appliance.
  • Page 10: General Instructions

    All installations and services must be performed by qualified service personnel. II. GENERAL INSTRUCTIONS The entire text of these instructions must be read and understood, before installing the appliance. It is the installer's responsibility to do the following: 1. Inform and demonstrate to the user, the correct operation and maintenance of the appliance, as explained in the Homeowner/User Information and Routine Maintenance section of this manual.
  • Page 11: Codes And Clearances

    All installations and services must be performed by qualified service personnel. A. Codes and Clearances: The following items must be considered when choosing the size and location of the unit. 1. All local codes and/or regulations take precedence over the instructions in this manual and should be followed accordingly.
  • Page 12: Selection Of Installation Location

    All installations and services must be performed by qualified service personnel. 5. Table 1 lists the required minimum clearances to combustible surfaces from the outer surfaces of the appliance. Table 1: Minimum Clearances to Combustible Materials Model Side Rear Front Bottom Vent Terminal (in.)
  • Page 13 All installations and services must be performed by qualified service personnel. surfaces. This clearance helps to promote air circulation under the base that allows the unit to be mounted on combustible materials. This clearance also helps to reduce metal corrosion caused by a buildup of moisture under the appliance.
  • Page 14: Venting Of Combustion Products

    All installations and services must be performed by qualified service personnel. condenser coil area are maintained. These openings are not to be blocked, or restricted, in any manner. 5. Measures should be taken to prevent the entry of corrosive chemicals or vapors to the combustion and ventilation air supply.
  • Page 15: Condensate Drain

    All installations and services must be performed by qualified service personnel. In addition, long term exposure of building materials to combustion products may cause discoloration of material surfaces and corrosion or degradation of materials. The preferred installation location will allow combustion products to freely escape the immediate area of the appliance and rapidly disperse into the atmosphere, without being drawn back into the appliance or a nearby structure.
  • Page 16: Oil Tank And Piping

    All installations and services must be performed by qualified service personnel. Figure 3: Installation of a Condensate Drainage Line on the Evaporator Coil Condensate from the evaporator is non-corrosive and may be disposed of in any appropriate manner. The drain connection should be sealed at the appliance housing to prevent air leakage from the supply air system.
  • Page 17 All installations and services must be performed by qualified service personnel. A readily accessible, design-certified, manual oil shutoff valve, with a non- displaceable rotor member, shall be installed in the fuel oil supply piping within 6 feet of the appliance. A pipe union, or flanged connection, shall be provided downstream from the manual oil shutoff valve to permit removal of the appliance oil pump.
  • Page 18: Oil Filter

    The appliance is supplied with two oil burner nozzles, one for the high-fire and one for the low-fire heat input rate. The model OPA has the low-fire, oil nozzle already installed in the burner by the factory. Table 2 gives the burner specifications and the estimated performance of the appliance operating under high and low fire conditions.
  • Page 19 All installations and services must be performed by qualified service personnel. Table 2: Burner Specifications and High and Low Fire Heating Performance Oil Pump Oil Flowrate Heat Input Heat Output Heating Burner Model Air Tube Nozzle Pressure @ Nozzle Rate* Rate** Mode Number...
  • Page 20: Airflow Requirements And Sizing Of Ductwork

    All installations and services must be performed by qualified service personnel. H. Airflow Requirements and Sizing of Duct Work The duct system must be sized and installed by a qualified installer or service person, following the design standards of the Air Conditioning Contractors of America (ACCA) or the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE).
  • Page 21 All installations and services must be performed by qualified service personnel. 6. The following method can be used to size ductwork when air velocities are low to moderate. a. Using a floor view of the residence, determine, or layout, the locations of the supply registers and the return air grills.
  • Page 22 All installations and services must be performed by qualified service personnel. h. The resistance of the take-off and the outlet register (or return grill) should then be summed together to determine the total pressure drop for each branch. This value should be close to the assumed value for the pressure drop of the system.
  • Page 23 All installations and services must be performed by qualified service personnel. Table 3: Suggested Duct Sizes for Homes, Quiet Offices, Or Similar Installations (Based on a 0.1 in. W.G. static pressure drop per 100 ft. of duct.) 7. The supply and return air ducts, or flexible joints, should be carefully secured and sealed to the appliance housing to prevent air leakage from, or into, the duct system.
  • Page 24: Air Filters

    If a method other than Thermo Pride filter racks is selected for retention of the filter and/or use of a different filter type is desired, refer to Table 4 for minimum sizing guidelines for selecting filter for the unit.
  • Page 25: Electrical Wiring

    All installations and services must be performed by qualified service personnel. J. Electrical Wiring : This appliance must be grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70-1999, or the latest edition. : Waterproof type connectors must be used when connecting electrical power and control wiring to the unit to prevent moisture from being drawn into the unit during operation.
  • Page 26 (if used), and the fan control module, inside the burner compartment. Consult the wiring diagram for the appropriate connection points on the thermostat and the fan control module. Table 5: Typical Electrical Requirements for Various OPA Models Maximum Compressor...
  • Page 27: Electronic Air Cleaner (Eac) And Humidifier Installation

    All installations and services must be performed by qualified service personnel. 3. All wiring sizes must comply with local codes or the National Electrical Code. To minimize voltage drop to the appliance, the next larger size wire should be used when long wiring runs, in excess of 100 ft., are employed. Refer to the wiring diagrams when wiring or servicing.
  • Page 28 All installations and services must be performed by qualified service personnel. Figure 4: The Fan Control Module NOTICE: It is important to confirm that the operating voltage of the humidifier or EAC being installed matches the output of this control. If not, a field supplied relay or transformer may be necessary to provide the proper control and supply voltage for the accessory being installed.
  • Page 29: Thermostat Anticipator Setting

    All installations and services must be performed by qualified service personnel. 2. Thermostat Anticipator Setting Proper control of the indoor air temperature can only be achieved if the thermostat is calibrated to the heating and/or cooling cycle. Calibration will help to produce a more constant indoor temperature by adjusting the length of the heating/cooling cycle to fit the application.
  • Page 30 All installations and services must be performed by qualified service personnel. Preferred method of adjustment: Using an analog ammeter on the lowest scale, such as an Amp Check, connect the meter across terminals “R” and “W” on the sub-base (“RH” & “W”...
  • Page 31: Blower Motor Speed Selection

    All installations and services must be performed by qualified service personnel. Or in this case, _2.5 A. = 0.25 A. (Anticipator Setting) iv. Adjust the position of the anticipator indicator to match the calculated ammeter setting. If a slightly longer cycle is desired, the pointer should be moved to a higher setting.
  • Page 32 All installations and services must be performed by qualified service personnel. Figure 7: Blower Motor Terminal Blocks & Wiring...
  • Page 33: Startup Procedures

    All installations and services must be performed by qualified service personnel. IV. STARTUP PROCEDURES A. Heating System 1. Initial Startup: : Turn off power to furnace. Before the oil piping system is placed into service, it must have been leak tested by a qualified heating contractor.
  • Page 34 All installations and services must be performed by qualified service personnel. For Your Safety Read Before Operating: : If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. •...
  • Page 35: Adjustment Of Burner Combustion

    All installations and services must be performed by qualified service personnel. ii. If service is to be performed, turn off the electrical power to the appliance. iii. Turn the manual oil shutoff valve to the “OFF” position. 2. Adjustment of Burner Combustion: : Maximum gross stack temperature must not exceed 550°F (288°C) under any circumstances.
  • Page 36 All installations and services must be performed by qualified service personnel. Open the inspection cover on the upper mounting plate above the burner. Turn the disconnecting switch to “ON”. Prime the pump to remove air in the oil supply line. When ignition is established, make a preliminary burner air adjustment to attain a clean combustion flame.
  • Page 37 All installations and services must be performed by qualified service personnel. NOTICE: To achieve proper combustion and the efficiencies listed in sales brochures, instruments must be used to secure or O readings. CARBON DIOXIDE (CO ) OR OXYGEN (O ): Take a CO sample from flue passageway.
  • Page 38: Adjustment Of Heat Input Rate

    All installations and services must be performed by qualified service personnel. The supply air temperature should be measured in the supply air trunkline approximately 12 inches downstream of the supply air outlet of the appliance. NOTICE: Minimum temperature rise is 50 F.;...
  • Page 39: Setting Supply Air Temperature Rise

    All OPA models are designed and wired at the factory for a blower speed during heating that should result in an approximate temperature rise of 65°F.
  • Page 40: Checkout Procedure

    All installations and services must be performed by qualified service personnel. After 15 to 20 minutes of continuous operation, the temperature rise through the furnace must fall within a range of 50° to 80° F. If the outlet or supply duct temperature is too high, check to make sure the return air filter is clean, the return air registers are free from obstruction, the outlet registers are properly adjusted and clear, and the supply and return air ducts are open.
  • Page 41 All installations and services must be performed by qualified service personnel. c. Make certain the thermostat will automatically start and stop the appliance. NOTICE: Heat exchanger oil will burn off on initial firing creating an unpleasant odor. To prevent this odor from occurring more than once, it is suggested the heating section be allowed to run for 30 minutes, or until odor has dissipated.
  • Page 42: Initial Startup

    All installations and services must be performed by qualified service personnel. B. Cooling Section 1. Initial Startup: : Refrigerant is under pressure. Guard against refrigerant spraying into the face or on skin. Always wear protective equipment, i.e. safety glasses or goggles and gloves when working with refrigerant. : Do not under any circumstances heat the refrigerant cylinder with a torch or by any other means other than warm water.
  • Page 43: Definition Of Superheat

    All installations and services must be performed by qualified service personnel. pressure-temperature chart on the unit for approximate system line pressures at various temperatures. The suction pressure is the most significant pressure reading. If a unit is suspected of having a low refrigerant charge, the unit should be recharged using the suction pressure as a guide.
  • Page 44: Evaporator Superheat

    To measure superheat at the evaporator, a suction pressure reading at the outlet of the evaporator would be desirable. Since most residential cooling systems (including Thermo Pride evaporators) do not provide a test port (sometimes referred to as a Schraeder port) at the evaporator, the suction pressure must be read at the suction inlet to the compressor.
  • Page 45: Definition Of Subcooling

    It is preferable to measure pressure of the liquid line at the evaporator, but most manufacturers, including Thermo Pride, do not include test ports (or Schraeder valves) at the evaporator. Typically, it would be necessary to compensate for the pressure drop through the line connecting the condenser and the expansion valve.
  • Page 46: Recommendations For Operation At Low Temperatures

    Refer to Example 4, in Appendix B: Calculations of this manual, for a sample calculation of how to figure the degree of subcooling for the condenser. In general, Thermo Pride recommends the evaporator operate with a subcooling of between 5° and 15°F.
  • Page 47: Installer's Instructions To User

    All installations and services must be performed by qualified service personnel. V. INSTALLER'S INSTRUCTIONS TO USER After completing the installation, the installer shall inform and/or demonstrate to the homeowner: 1. The location of these instructions in the appliance. These instructions must be kept along with instructions for any accessories in the plastic pouch on the inside of the appliance.
  • Page 48: Dealer Maintenance

    All installations and services must be performed by qualified service personnel. VI. DEALER MAINTENANCE SAFETY DURING SERVICING AND INSPECTION : Personal injury or property damage could result from repair or service of this appliance by anyone other than a qualified heating contractor. The user may only perform the activities described in the Homeowner/User Routine Maintenance section of this manual.
  • Page 49: Heat Exchanger

    All installations and services must be performed by qualified service personnel. excessive wear. Replace it, if required. Check and adjust oil pump pressure, if needed. Refer to Initial Heating System Adjustments section of this manual. 4. Heat Exchanger – Visually inspect the heat exchanger for excessive carbon (soot) build-up.
  • Page 50 All installations and services must be performed by qualified service personnel. Figure 9, OPA Heat Exchanger Clean-out Ports and Related Components Remove the clean-out covers. Also, remove the burner compartment cover, the burner, and the burner mounting plate. When removing the clean-out covers, special care must be taken not to damage the gaskets.
  • Page 51: Reassembly Of Unit

    Reset the burner, as indicated under the Initial Burner Operation section. Figure 10: View of OPA Heat Exchanger Replace any damaged or corroded components. All gaskets and insulation must be inspected, and replaced, if they show any signs of damage.
  • Page 52: Operational Check

    All installations and services must be performed by qualified service personnel. 3. Operational Check : Before troubleshooting, familiarize yourself with the start up and check out procedures NOTICE: After reassembling the appliance, check for fuel oil leakage from the supply piping. a.
  • Page 53: Supply/Return Air Blower

    If the filter has a supporting mesh, the mesh side of the filter must be placed towards the furnace. Figure 12: Location of the OPA Supply/Return Air Filter 2. Filter replacement To ensure an adequate replacement filter is selected, should the filter require replacing, refer to Table 4, in Air Filters section of this manual, for the minimum filter areas required for different types of available filters.
  • Page 54: Extended Appliance Shutdown

    All installations and services must be performed by qualified service personnel. NOTICE: Remind the homeowner of the importance of monthly filter inspections during operation to ensure maximum operating efficiency. F. Extended Appliance Shutdown : Do not attempt to start burner when: •...
  • Page 55 All installations and services must be performed by qualified service personnel. Open the inspection cover on the upper mounting plate. Turn on the electrical power to start the burner. If the burner does not start, immediately reset the manual overload switch on the motor (if so equipped) and the safety switch of the burner primary control.
  • Page 56: Homeowner/User Information And Routine Maintenance

    All installations and services must be performed by qualified service personnel. VII. HOMEOWNER/USER INFORMATION AND ROUTINE MAINTENANCE : Never burn garbage or refuse in this appliance. Never try to ignite oil by tossing burning papers or other material into the combustion chamber. : Oil-fired appliances produced by Thermo Products are designed for burning No.
  • Page 57 All installations and services must be performed by qualified service personnel. 4. Check to see if the high temperature limit switch reset button, on the burner motor, has “popped out”. If so, the control has activated. To reactivate the control, depress the reset button. 5.
  • Page 58 All installations and services must be performed by qualified service personnel. The following maintenance points should be reviewed periodically to assure the heating and cooling systems continue to function properly. : Shut off unit and disconnect the power source before disassembling the unit.
  • Page 59 All installations and services must be performed by qualified service personnel. ducts for any signs of collapse, holes, or excessive corrosion. Repair or replace components as required. 8. It is advisable to wax the outer surface of the appliance housing yearly to provide the surface finish protection from excessive degradation by sunlight and inclement weather.
  • Page 60: Troubleshooting

    All installations and services must be performed by qualified service personnel. VIII. TROUBLESHOOTING : Power must be disconnected before servicing. Refer to the appendices of this manual for an electrical schematic, a connection diagram, flowcharts to assist in troubleshooting, product specifications, and a replacement parts list follow for this appliance.
  • Page 61: Cooling System

    All installations and services must be performed by qualified service personnel. The operational condition of the flame sensor, or “cad cell”, can be checked by depressing the reset button on the control module, while the burner is operating. Count the number of flashes of the LED and compare them to the table below. Number of flashes Cad Cell Resistance (in ohms) Model R7184P...
  • Page 62 All installations and services must be performed by qualified service personnel. 1. Is the disconnect switch or the circuit breaker serving the appliance switched on? If equipped, have the disconnect switch fuses “blown” or has the circuit breaker tripped? If an electrical fault has occurred more than once, call your qualified service person to diagnose the cause and perform the required repair(s).
  • Page 63: References

    All installations and services must be performed by qualified service personnel. REFERENCES 1. International Approval Services-U.S. Inc. and the National Fire Protection Association, 1996, National Fuel Gas Code, ANSI Z223.1-1996/NFPA 54-1996, 6th Ed., pp. 10 & 13. 2. Earley, M.W., Sheehan, J.V., Caloggero, J.M., 1999, National Electrical Code Handbook, 8th Ed., National Fire Protection Assoc., Inc., pp.
  • Page 64: Appendix A: Sources For Referenced Standards

    All installations and services must be performed by qualified service personnel. APPENDIX A: SOURCES FOR REFERENCED STANDARDS 1. Air Conditioning Contractors of America 1712 New Hampshire Avenue, NW Washington, D.C. 20009 (202) 483-9370 2. American National Standards Institute, Inc., Attn: Customer Service 11 West 42 Street New York, New York 10036...
  • Page 65: Appendix B: Calculations

    All installations and services must be performed by qualified service personnel. APPENDIX B: CALCULATIONS Example 1: Problem: It is desired to install a warm-air furnace w/ an air conditioning evaporator coil at a residence. The net output of the furnace is 100,000 BTU/hr and the evaporator will provide 4 tons of cooling to the space.
  • Page 66 All installations and services must be performed by qualified service personnel. Figure 15: Plan View of a Typical Residence Solution: If certain flowrates are desired, for heating or cooling reasons, or are required, by local codes, those guidelines should be followed. In lieu of other requirements, room floor area can be used to select flowrates for each room.
  • Page 67 All installations and services must be performed by qualified service personnel. This procedure can be repeated to determine the airflow for each room in the residence. The results of these calculations are given in Table 6, below. Table 6: Required Room Air Flowrates Based on Floor Area for Example 2 Room Room Air...
  • Page 68 All installations and services must be performed by qualified service personnel. Therefore, choose a supply system static pressure drop of 0.2 in. W.G. (Then, the return air system will also have a static pressure drop of 0.2 in. W.G.) Furthermore, we will assume that the static pressure drops for all registers in the supply system will be 0.1 in.
  • Page 69 All installations and services must be performed by qualified service personnel. However, there are two, 90 degree turns in the branch that will cause a large pressure drop, not accounted for in our calculations. To compensate for this drop, we should increase the effective length of the branch. For a 90 degree, mitered elbow, the equivalent straight duct length is given by the following formula, elbow...
  • Page 70 All installations and services must be performed by qualified service personnel. For section “C”, including a 7-inch, 90-degree elbow, the pressure drop is, 00123174 ∆ 0257 Likewise, the pressure drops for the two remaining segments in this branch can be calculated in the same manner. They are, ∆...
  • Page 71 All installations and services must be performed by qualified service personnel. Next, the branch of the system, which includes segments “D” and “E” can be evaluated. To balance the system, the pressure drop for segments “D” and “E” combined must be approximately equal to the pressure drops of segments “A”, “B”...
  • Page 72 All installations and services must be performed by qualified service personnel. 2058 ⎡ ⎤ 00123174 ≅ ⎢ ⎥ 0614 ⎣ ⎦ or an increase in duct size of about 1 inch in diameter. The pressure drops for the remaining branches of the system must be set. This includes segment “G”;...
  • Page 73 All installations and services must be performed by qualified service personnel. Example 3: Problem: Refrigerant measurements are made on the cooling system of a typical GPA installation. The suction line pressure, measured at the condenser unit, suction line, charging port, is 68 PSIG. The temperature of the refrigerant (R22) at the evaporator suction line connection is measured as 48 °...
  • Page 74 All installations and services must be performed by qualified service personnel. Now, the degree of superheat can be calculated. 48 ° F (Suction line temperature at outlet of evaporator) - 40 ° F (Saturation temperature for R22 at 68 PSIG) ----------------------- 8 °...
  • Page 75 All installations and services must be performed by qualified service personnel.
  • Page 76: Appendix C: Electrical Schematic And Connection Diagram

    All installations and services must be performed by qualified service personnel. XII. APPENDIX C: ELECTRICAL SCHEMATIC AND CONNECTION DIAGRAM...
  • Page 77: Appendix D: Sequence Of Operations

    All installations and services must be performed by qualified service personnel. XIII. APPENDIX D: SEQUENCE OF OPERATIONS 1 of 2 A. SEQUENCE OF OPERATIONS FOR THE HEATING SYSTEM Mode of Operation Control System Action Standby (At any time the oil Continous safe operation check.
  • Page 78 All installations and services must be performed by qualified service personnel. 2 of 2 Mode of Operation Control System Action After 45 second delay, the ignition electrodes are de- energized. The circulating air fan is energized at heating Main Burner speed.
  • Page 79: Appendix E: Troubleshooting Flowcharts

    All installations and services must be performed by qualified service personnel. XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS TURN THERMOSTAT TO CALL FOR HEAT DOES THERMOSTAT MAKE CONTACT? IS ROOM TEMPERATURE TURN T'STAT SETTING IS ROOM TEMPERATURE ABOVE ROOM BELOW THERMOSTAT SETTING? TEMPERATURE ALLOW THE ROOM AIR TO COOL...
  • Page 80 All installations and services must be performed by qualified service personnel. IS IGNITION ESTABLISHED? IS IGNITION TRANSFORMER ARE THE ELECTRODES REPLACE IGNITION CAPABLE OF PRODUCING A ARCING? TRANSFORMER 3/4" ARC? (10,000 VAC) DETERMINE IF THE ELECTRODES ARE ALIGNED, CONTACT SPRINGS TOUCHING ELECTRODE RODS, &...
  • Page 81 All installations and services must be performed by qualified service personnel. PROPER COMBUSTION ACHIEVED? IS THE AIR TUBE INSERTION CORRECT INSERTION OR IS THE PROBLEM DELAYED 0-1/4" BACK FROM INSIDE AIR TUBE BURNOFF IGNITION? OF REFRACTORY? MAY OCCUR. ALIGN ELECTRODES PER ARE THE ELECTRODES BURNER INSTRUCTION PROPERLY ALIGNED?
  • Page 82 All installations and services must be performed by qualified service personnel. DOES FURNACE OPERATE WITHOUT CONDENSING? IS STACK TEMPERATURE IS BURNER SET AS INDICATED ADJUST BURNER COMBUSTION IN ABOVE SECTION? TO PRODUCE ZERO SMOKE. SLOW THE BLOWER SPEED IS THE TEMPERATURE TO RAISE TEMPERATURE DIFFERENCE BETWEEN SUPPLY RISE.
  • Page 83 All installations and services must be performed by qualified service personnel.
  • Page 84 All installations and services must be performed by qualified service personnel. Notes for Air Conditioning Troubleshooting Guide 1.101.0 Check to see if the contactor has not pulled in. If the coil has not pulled in the contactor, check for 24 VAC to the coil on the contactor. 1.101.1 Check to make sure the control transformer is powering the 115 VAC circuit.
  • Page 85 All installations and services must be performed by qualified service personnel. 2.101.0 Check to see if the condenser fan motor is excessively hot as to cause the thermal-overload to function. Possible causes for outdoor fan motor to kick off on overload are: 1) Loose wire connections.
  • Page 86 All installations and services must be performed by qualified service personnel. 3.101.1 Dirty air filters may restrict the airflow across the evaporator coil resulting in frost on the coil. 3.101.2 Are the duct system and air blower setup to move enough air to have an 18-20 degree F.
  • Page 87: Appendix F: Specification Sheets

    All installations and services must be performed by qualified service personnel. APPENDIX F: SPECIFICATION SHEETS Model No.: OPA24-80 OPA30-80 OPA36-80 OPA42-80 Heating Performance (using # 2 fuel oil): Input rate (BTUH), Maximum / Minimum : 105,000 / 85,000 Heating capacity (BTUH), Maximum / Minimum : 85,000 / 68,000 Design temp.
  • Page 88: Appendix G: Replacement Parts

    All installations and services must be performed by qualified service personnel. APPENDIX G : REPLACEMENT PARTS LIST...
  • Page 89 All installations and services must be performed by qualified service personnel.
  • Page 90: Appendix H: Opa Heating And Cooling Test Form

    All installations and services must be performed by qualified service personnel. XVI. APPENDIX H: OPA HEATING AND COOLING SYSTEMS TEST FORM Complete this form for each Thermo Pride OPA appliance installed. Read the instruction manual carefully before making tests. Retain this form with appliance. Name:...

This manual is also suitable for:

Opa24-80Opa30-80Opa36-80Opa42-80

Table of Contents